3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. <br />Exception: Where floor areas adjacent to an exit passageway are reachable from an inteFieF exit <br />stairway hose connection by a a 30 -foot (9144 mm) hose stream from a nozzle attached to 100 <br />feet (30 480 mm) of hose, a hose connection shall not be required at the entrance from the exit <br />passageway to other areas of the building. <br />4. In covered mall buildings, adjacent to each exterior public entrance to the mall and adjacent to <br />each entrance from an exit passageway or exit corridor to the mall. In open mall buildings, <br />adjacent to each public entrance to the mall at the perimeter line and adjacent to each entrance <br />from an exit passageway or exit corridor to the mall. <br />5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3 - percent slope), <br />each standpipe shall be provided with a two -way a -hose connection shall be located to serve the <br />roof or at the highest landing of an inteFieF exit stairway with stair access to the roof provided in <br />accordance with Section 1011.12. <br />6. Where the most remote portion of a non - sprinklered flor or story is more than 150 feet (45 720 <br />mm) from a hose connection or the most remote portion of a sprinklered floor or story is more than <br />200 feet (60 960 mm) from a hose connection, the fire code official is authorized to require that <br />additional hose connections be provided in approved locations. <br />7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits <br />to the structure and at two hundred feet (200') intervals along major corridors thereafter, or as <br />otherwise approved by the fire code official. <br />Section 905.9, Valve supervision, shall be amended to add a second paragraph after the <br />Exceptions to read as follows: <br />[F] Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the <br />sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds All <br />control valves in the sprinkler and standpipe systems except for fire department hose connection valves <br />shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. <br />Section 907.1, General, shall be amended to add Section 907.1.4, Design standards, to read as <br />follows: <br />[F] 907.1.4 Design standards. Where a new fire alarm system is installed the devices shall be <br />addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog initiating <br />devices. <br />Section 907.2.1, Group A, shall be amended to read as follows: <br />[F] 907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in <br />accordance with Section 907.5 shall be installed in Group A occupancies wheFe the having an occupant <br />load due te the assembly 9GOUpaRGY is of 300 or more persons or more than 100 persons above or below <br />the lowest level of exit discharge. Group A occupancies not separated from one another in accordance <br />with Section 707.3. -10 of the International Building Code shall be considered as a single occupancy for <br />the purposes of applying this section. Portions of Group E occupancies occupied for assembly purposes <br />shall be provided with a fire alarm system as required for the Group E occupancy. <br />Exception: Manual fire alarm boxes are not required where the building is equipped throughout <br />with an automatic sprinkler system installed in accordance Section 903.3.1.1 and the occupant <br />notification appliances will activate throughout the notification zones upon sprinkler water flow. <br />Activation of fire alarm notification appliances shall: <br />1. Cause illumination of the means of egress with light of not less than 1 foot - candle (11 lux) at the <br />walking surface level, and <br />2. Stop any conflicting or confusing sounds and visual distractions <br />Section 907.2.3, Group E, shall be amended to read as follows: <br />[F] 907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an <br />emergency voice /alarm communication system meeting the requirements of Section 907.5.2.2 and <br />installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When <br />8 2015 IBC Amendments <br />