Laserfiche WebLink
"Exceptions: <br />"1. Tents, as provided for in Chapter 31. <br />"2. A Type I hood shall not be required for an electric cooking <br />appliance where and approved testing agency provides <br />documentation that the appliance effluent contains 5 mg/m3 or <br />less of grease when tested at an exhaust flow rate of 500 cfm <br />(0.236 m3/s) in accordance with UL 71013. <br />"Additionally, fuel gas and power provided for such cooking appliances <br />shall be interlocked with the extinguishing system, as required by Section <br />904.12.2. Fuel gas containers and piping/hose shall be properly maintained <br />in good working order and in accordance with all applicable regulations." <br />Section 704.1, Enclosure, shall be amended to read as follows: <br />"704.1 Enclosure. Interior vertical shafts including, but not limited to, <br />stairways, elevator hoistways, service and utility shafts, that connect two or <br />more stories of a building shall be enclosed or protected in accordance with <br />the codes in effect at the time of construction but, regardless of when <br />constructed, not less than as required in Chapter 11. New floor openings in <br />existing buildings shall comply with the International Building Code." <br />Section 807.3, Combustible decorative materials, shall be amended to read as <br />follows: <br />"807.3 Combustible Decorative Materials. In occupancies in Groups <br />A, E, I, and R-1, and dormitories in Group R-2, curtains, draperies, fabric <br />hangings and other similar combustible decorative materials suspended from <br />walls or ceilings shall comply with Section 807.4 and shall not exceed 10 <br />percent of the specific wall or ceiling area to which they are attached." <br />Sections 807.5.2.2, Artwork in corridors, and 807.5.2.3, Artwork in classrooms, <br />shall be amended to read as follows: <br />"807.5.2.2 Artwork in Corridors. Artwork and teaching materials <br />shall be limited on the walls of corridors to not more than 20 percent of the <br />wall area. Such materials shall not be continuous from floor to ceiling or wall <br />to wall. Curtains, draperies, wall hangings, and other decorative material <br />suspended from the walls or ceilings shall meet the flame propagation <br />performance criteria of NFPA 701 in accordance with Section 807 or be <br />noncombustible. <br />21 <br />