shall be provided for smokeproof enclosures, stair pressurization alternative and associated <br />automatic fire detection systems as required by the International Building Code, Section <br />909.20.7.2. <br />1203.2.23 Elevator Pressurization. Standby power shall be provided for elevator pressurization <br />system as required by the International Building Code, Section 909.21.5. <br />1203.2.24 Elimination of Smoke Dampers in Shaft Penetrations. Standby power shall be <br />provided when eliminating the smoke dampers in ducts penetrating shafts in accordance with <br />the International Building Code, Section 717.5.3, exception 2.3. <br />1203.2.25 Common Exhaust Systems for Clothes Dryers. Standby power shall be provided <br />for common exhaust systems for clothes dryers located in multistory structures in accordance <br />with the International Mechanical Code, Section 504.11, item 7. <br />1203.2.26 Means of Egress Illumination in Existing Buildings. Emergency power shall be <br />provided for means of egress illumination in accordance with Section 1104.5 when required by the <br />fire code official. (90 minutes in 1-2,60 minutes elsewhere.) <br />1203.3 through 1203.6 {No change.} <br />Amend Section 2304. 1, Supervision of dispensing, to read as follows: <br />Supervision of dispensing. The dispensing of fuel at motor fuel -dispensing facilities shall be <br />in accordance with the following: <br />1. Conducted by a qualified attendant; and/or, <br />2. Shall be under the supervision of a qualified attendant; and/or <br />3. Shall be an unattended self-service facility in accordance with Section 2304.3. <br />At any time the qualified attendant of item Number 1 or 2 above is not present, such operations <br />shall be considered as an unattended self-service facility and shall also comply with Section 2304.3. <br />Delete Section 2401.2, Nonapplicability, in its entirety. <br />Delete Section 3103.3.1, Special amusement area, in its entirety. <br />Amend Table 3206.2, General Fire Protection and Life Safety Requirements, footnote h, and add <br />footnote j, to read as follows: <br />h. Where storage areas are protected by either early suppression fast response (ESFR) sprinkler <br />systems or control mode special application sprinklers with a response time index of 50 (m x <br />s) 1/2 or less that are listed to control a fire in the stored commodities with 12 or fewer <br />sprinklers, installed in accordance with NFPA 13, manual smoke and heat vents or manually <br />activated engineered mechanical smoke exhaust systems shall be required within these areas. <br />j. High hazard high -piled storage areas shall not exceed 500,000 square feet. A 2 -hour fire <br />wall constructed in accordance with Section 706 of the International Building Code shall be used <br />to divide high -piled storage exceeding 500,000 square feet in area. <br />