Laserfiche WebLink
dimension of the lot or area to be served, measured in a straight line between accesses, or as <br />approved by the fire code official. <br />Amend Section D105.3, Proximity to building, to read asfollows: <br />D105.3 Proximity to building. Unless otherwise approved by the fire code official, one or more of <br />the required access routes meeting this condition shall be located not less than 15 feet (4572 mm) <br />and not greater than 30 feet (9144 mm) from the building, and shall be positioned parallel to one <br />entire side of the building. The side of the building on which the aerial fire apparatus access road <br />is positioned shall be approved by the fire code official. <br />Amend Section D106.3, Remoteness, to read as follows: <br />D106.3 Remoteness. Where two fire apparatus access roads are required, they shall be placed a <br />distance apart equal to not less than one-half of the length of the maximum overall diagonal <br />dimension of the property or area to be served, measured in a straight line between accesses, or <br />as approved by the fire code official. <br />Amend Section D107.2, Remoteness, to read as follows: <br />D107.2 Remoteness. Where two fire apparatus access roads are required, they shall be placed a <br />distance apart equal to not less than one-half of the length of the maximum overall diagonal <br />dimension of the property or area to be served, measured in a straight line between accesses, or <br />as approved by the fire code official. <br />(Reason: To provide some additional flexibility to the fire code official on the location of the two <br />fire apparatus access roads.) <br />Amend Appendix L, Requirements For Fire FighterAir Replenishment Systems, as follows: <br />Amend Section L101.1, Scope, to read as follows: <br />L101.1 Scope. Fire fighter air replenishment systems (FARS) shall be provided in accordance with <br />this appendix in new buildings when any of the following conditions occur: <br />1. Any new building 5 or more stories in height. <br />2. Any new building with 2 or more floors below grade. <br />3. Any new building 500,000 square feet or more in size. <br />Each stairwell shall have a supply riser. SCBA fill panels shall be located on odd numbered floors <br />commencing at the first level in the primary stairwell and on even numbered floors commencing at <br />level 2 in the remaining stairwells. Fill panels in buildings over 500,000 square feet shall be located <br />adjacent to each standpipe connection. <br />Delete Section L104.13.1, Location, in its entirety. <br />Amend Section L104.14, External mobile air connection, to add the following paragraph: <br />