4. [Unchanged.] <br />S. Where the roof has a slope less than 4 units vertical in 12 units horizontal <br />(33.3 -percent slope), each standpipe shall be provided with a two-way a hose <br />connection located to serve the roof or at the highest landing of an exit stairway <br />with stair access to the roof provided in accordance with Section 1011.12. <br />6. [Unchanged.] <br />7. When required by this Chapter, standpipe connections shall be placed <br />adjacent to all required exits to the structure and at two hundred feet (2003 <br />intervals along major corridors thereafter, or as otherwise approved by the fire <br />code official. <br />Amend Section 905.8, Dry standpipes, to read as follows: <br />905.8 Dry standpipes. Dry standpipes shall not be installed. <br />Exception: Where subject to freezing and in accordance with NFPA 14. Additionally, <br />manual dry standpipe systems shall be supervised with a minimum of 10 psig and a <br />maximum of 40 psig air pressure with a high./low alarm. <br />Amend Section 905.9, Valve supervision, by adding a second paragraph after the <br />Exceptions to read as follows: <br />905.9 Valve supervision. [Existing text unchanged.] <br />Exceptions: [Exceptions unchanged. <br />Sprinkler and standpipe system water -flow detectors shall be provided for each <br />floor tap to the sprinkler system and shall cause an alarm upon detection of water <br />flow for more than 45 seconds. All control valves in the sprinkler and standpipe <br />systems except for fire department hose connection valves shall be electrically <br />supervised to initiate a supervisory signal at the central station upon tampering. <br />Amend Section 906.1, Where required, subsection (1-), by deleting Exception #3. <br />Amend Section 907.1, General, b ay dding Section 907.1.4, Design standards, to read as <br />follows: <br />907.1.4 Design standards. Where a new fire alarm system is installed, the <br />devices shall be addressable. Fire alarm systems utilizing more than 20 smoke <br />detectors shall have analog initiating devices. <br />16 <br />
The URL can be used to link to this page
Your browser does not support the video tag.