Laserfiche WebLink
Amend Section.. 903.3.1.2.3.,d <br />-Attache-- and attics,, to -read as ollows:. <br />903.3.1.2.3 Attached ara es,.,and attics. S err nkler, -j;,)rotection is r quired in <br />attached garages and in the followingatt c._s.l aces: <br />1. Attics that are used or intended for livino purposes orstorage ,shall be <br />)rotected by an automatic s : rinkler s stem. <br />2. Where ..fuel -fired -.e ui ment is installed in an unslarinklered attic not fewer <br />than one g uick-res onse intermediate tem )erature s ,)rinkler shall be installed <br />above the euiiment. <br />3. Attic spaces of buildings that are two or more stories in height. above_grade <br />plane or above the lowest level of fire de artment vehicle access. <br />4. Grout) R-4, Condition.2 occulanc attcs...not Wre uired b Item 1 or 3 to have. <br />sprinklers shall comply with one of the followinl�; <br />4,1 _.IT...Provide automatic s irin ler ss stem protection, <br />4.2. Provide a heat detections stem throughout the attic that is arranged <br />to activate the buildin µfire_alarms stem. <br />4.3. Construct the attic using noncombustibl materials. <br />4.4. Construct the attic using..fire-retardant-treated wood c0nlDlyina with <br />Section 2303.2 of the International Building Code. <br />4.5. Fill the attic with noncombu tibl insulation. <br />Amend Section 903.,3.1_.,3, NFPA 13D sprinkler sy tems to read as oflows: <br />903.3.1.3 NFPA 13D s rinkler s stems. Automatic sharnkler s stems installed <br />in one-..andtwo-family dwellings: Grou 3 R-3• Groups R-4, Condition 1„ and <br />townhouses shall be .t)_ermitted to be installed throughout in accordance with, <br />NFPA 13D or in accordance with state law. <br />Amend Section 903.3.1.4, Freeze protection, to read as follows: <br />F 903.3.1.4 Freeze protection. Freeze„ protection s stems for automatic fire <br />sprinkler systems shall be in accordance with the re,urementsMof.the alicable <br />referenced NFPA standard and this section. <br />Add Section 903.3.1.4.1., Attics, to read as follows: <br />903.3.1.4.1 _Attics. Onl dpwe reaction. or listed antifreeze automatic fire <br />sprinkler ssir temsIT.shall be allowed to pirotect.attic s rad ces. <br />Exception: Wet-Dipefire sl rinkler s �stems_shallIT be allowed to :protect non- <br />ventilated attic spaces where.: <br />13 <br />