Laserfiche WebLink
Sprinkler system risers providing protection for buildings <br />with multiple tenant spaces must be located in a ground floor <br />room directly accessible from the exterior. The door must be <br />labeled as the riser room. Buildings with single tenants may <br />access the riser location from the interior of the building. <br />Section 903.4, Sprinkler systems monitoring and alarms, shall be <br />amended to add a second paragraph after the Exceptions, to read as <br />follows: <br />Sprinkler and standpipe system water-flow detectors shall <br />be provided for each floor tap to the sprinkler system and shall <br />cause an alarm upon detection of water flow for more than 45 <br />seconds. All control valves in the sprinkler and standpipe <br />systems, except for fire department hose connection valves, <br />shall be electrically supervised to initiate a supervisory signal at <br />the central station upon tampering. <br />Section 903.4.2, Alarms, shall be amended to add a second <br />paragraph to read as follows: <br />The alarm device required on the exterior of the building <br />shall be a weatherproof horn-strobe notification appliance with <br />a minimum 75 candela strobe rating, installed as close as <br />practicable to the fire department connection. <br />Section 903.6.2, Spray booths and rooms, shall be added to read as <br />follows: <br />Spray booths and spray rooms installed, constructed, or <br />remodeled after the adoption of this code shall be protected by <br />an approved automatic fire-extinguishing system in accordance <br />with Section 1504. <br />Section 905.2, Installation standard, shall be amended to read as <br />follows: <br />Standpipe systems shall be installed in accordance with <br />this section and NFPA 14. Manual dry standpipe systems shall <br />be supervised with a minimum of 10 psig and a maximum of 40 <br />psig air pressure with a high/low alarm. <br />23 <br />A 'I;QV075 <br />