Section 910.3.2.2, Sprinklered buildings, shall be amended by adding a <br />second paragraph to read as follows: <br />The automatic operating mechanism of the smoke and <br />heat vents shall operate at a temperature rating at least 100 <br />degrees (F) (approximately 38 degrees Celsius) greater than the <br />temperature rating of the sprinklers installed. <br />Section 912.3.1, Locking fire department connection caps, shall be <br />amended to read as follows: <br />The Fire Code Official is authorized to require locking caps <br />on existing fire department connections for water-based fire <br />protection systems where the responding fire department <br />carries appropriate key wrenches for removal. Locking caps are <br />required on all fire department connections for water-based <br />fire protection systems installed or modified after the adoption <br />of this code. <br />Section 913.1, General, shall be amended by adding a second paragraph <br />and exception to read as follows: <br />When located on the ground level at an exterior wall, the <br />fire pump room shall be provided with an exterior fire <br />department access door that is not less than 3 ft. in width and 6 <br />ft. - 8 in. in height, regardless of any interior doors that are <br />provided. A key box shall be provided at this door, as required <br />by Section 506.1. <br />Exception: <br />When it is necessary to locate the fire pump room on <br />other levels or not at an exterior wall, the corridor leading <br />to the fire pump room access from the exterior of the <br />building shall be provided with equivalent fire resistance <br />as that required for the pump room, or as approved by the <br />Fire Code Official. Access keys shall be provided in the key <br />box as required by Section 506.1. <br />Section 1008.1.3.4, Access-controlled egress doors, criterion #7 shall be <br />added to read as follows: <br />7. If a full building smoke detection system is not <br />provided, approved smoke detectors shall be <br />provided on both the access and egress sides of doors <br />29 <br />a u 0 li0 8 -liL <br />