Laserfiche WebLink
5. Separation of occupants in the assembly area from the warehousing of goods or <br />merchandise is required. <br />6. Area where drop ceiling tile is provide prevents the vertical travel of fire spread. So the <br />tiles missing should be replaced and the tiles that are not positioned or seated correctly in <br />grid need to be corrected. <br />7. Kitchen area is conducting commercial cooking that produces grease laden vapors, and <br />requires vent a hood, with fixed suppression system and a type K extinguisher. <br />Ail violations in this report are violations of International Fire Code 2006 3rd printing 2007 and its <br />referenced codes and standards as adopted by the City of Paris Ordinance NO. 2010-028. <br />Clyde Crews 1269 <br />Fire Marshal City of Paris <br />