Loading...
10 - DISCUSS AND ACT ON AMENDING ORDINANCE... 2015 INTERNATIONAL FIRE CODEORDINANCE NO. AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF PARIS, TEXAS; AMENDING CHAPTER 12 OF THE CODE OF ORDINANCES OF THE CITY OF PARIS, AMENDING ARTICLE III, "FIRE CODE," TO REPEAL THE 2006 EDITION OF THE INTERNATIONAL FIRE CODE AND TO ADOPT THE 2015 EDITION OF THE INTERNATIONAL FIRE CODE; ESTABLISHING LOCAL AMENDMENTS TO THE 2015 EDITION OF THE INTERNATIONAL FIRE CODE; PROVIDING FOR ENFORCEMENT; MAKING OTHER FINDINGS AND PROVISIONS RELATED TO THE SUBJECT; PROVIDING A REPEALER CLAUSE, A SEVERABILITY CLAUSE, A SAVINGS CLAUSE, A PENALTY CLAUSE; AND PROVIDING FOR AN EFFECTIVE DATE. WHEREAS, the City of Paris has previously adopted the 2006 International Fire Code promulgated by the International Code Council; and WHEREAS, from time to time, the International Code Council has issued new editions of the International Fire Code reflecting updated standards, the most recent edition having been issued in 2015; and WHEREAS, the Fire Chief and Fire Marshal of the Paris Fire Department hereby recommend that the City adopt said 2015 edition of the International Fire Code to keep pace with current standards, to ensure the safety of buildings within the City and to enhance the safety and health of the citizens of and visitors to the city; and, WHEREAS, the City Council deems it to be in the best interest of the City of Paris and its citizens to repeal the existing 2006 Fire Prevention Code and to adopt the 2015 Edition of the International Fire Code as amended with local amendments as set out below; NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF PARIS, TEXAS, THAT: Section 1. The findings set out in the preamble to this ordinance are hereby in all things approved. Section 2. Sections 12 -51, 12 -52 and 12 -53 of Chapter 12, Article III of the Code of Ordinances of the City of Paris, "Fire Code," are hereby amended to read in their entirety as follows: "ARTICLE III. FIRE CODE Sec. 12 -51. Adoption of the 2015 International Fire Code There is hereby adopted by the City Council of the City of Paris, Texas, 1 for the purpose of prescribing regulations governing conditions hazardous to life and property, those certain codes known as the 2015 Edition of the International Fire Code, Appendices A, B, C, D, E, F, G, H, I, J, K, L and M to the same extent as if such Code were copied verbatim in this Article subject to local amendments as set forth in this Article. Copies of the Codes and the amendments thereto, as referenced herein, are on file in the office of the City Clerk, City of Paris for permanent record and inspection. These copyrighted standards and recommendations are adopted and designated as the official Fire Code of the City of Paris, except to the extent they are in conflict with any controlling Federal or State law. The standards are published by and are available from the International Code Council, Country Club Hills, Illinois. A copy of the 2015 International Fire Code along with a copy of the amendments adopted herein shall be kept in each of the following locations: The Paris City Library, the City Clerk's office, the Paris Fire Marshal's office and the office of the City Engineer and the City's Planning & Development office. Sec. 12-52. Definitions. (a) Jurisdiction shall mean the corporate city limits of the City of Paris, Texas. (b) Fire Code Official or Fire Chief shall mean the Fire Marshal of the City of Paris Fire Department. (b) Person shall mean any person, firm, partnership, association, corporation or other legal entity. Sec. 12 -53. Fire Code Amendments. The following local amendments repeal or add sections to the 2015 International Fire Code. These amendments shall supersede, replace and /or supplement the 2015 International Fire Code as follows: Section 101.1, Title, shall be amended to read as follows: "These regulations shall be known as the FIRE CODE of the City of Paris, Texas hereinafter referred to as `this Code. "' Section 102.1, subsection 3, Scope, shall be amended to read as follows: "3. Existing structures, facilities, and conditions when required in Chapter 11 or in specific sections of this code." Section 102.4, Application of the Building Code, shall be amended to read as 2 follows: "102.4 Application of the Building Code. The design and construction of new structures shall comply with this Code and the other codes as adopted by the City of Paris, Texas; and any alterations, additions, changes in use or changes in structures required by this Code shall be made in accordance therewith." Section 102.7, Referenced codes and standards, shall be amended to read as follows: "102.7 Referenced codes and standards. The codes and standards referenced in this Code shall be those that are listed in Chapter 80, and such codes and standards shall be considered part of the requirements of this Code to the prescribed extent of each such reference. Where differences occur between the provisions of this Code and the referenced standards, the provisions of this Code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 (National Electrical Code) shall mean the Electrical Code as adopted by the City of Paris." Section 105.3.3, Occupancy prohibited before approval, shall be amended to read as follows: "105.3.3 Occupancy prohibited before approval. The building or structure shall not be occupied prior to the fire code official issuing a permit when required and conducting associated inspections indicating the applicable provisions of this code have been met." Section 105.6, Required operational permits, shall be amended by deleting the following subsections: 105.6.1, 105.6.2, 105.6.3, 105.6.5, 105.6.6, 105.6.7, 105.6.8, 105.6.9, 105.6.10, 105.6.11, 105.6.12, 105.6.13, 105.6.14, 105.6.18, 105.6.19, 105.6.20, 105.6.21, 105.6.22, 105.6.23, 105.6.25, 105.6.26, 105.6.27, 105.6.28, 105.6.29, 105.6.30, 105.6.31, 105.6.33, 105.6.34, 105.6.35, 105.6.36, 105.6.37, 105.6.39, 105.6.40, 105.6.41, 105.6.42, 105.6.43, 105.6.44, 105.6.45, 105.6.46, 105.6.47 and 105.6.48. Section 105.6.16, Fire hydrants and valves, shall be amended to read as follows: "105.6.16 Fire hydrants and valves. An operational permit is required to use or operate fire hydrants or valves intended for fire suppression purposes which are installed on water systems and accessible to a fire apparatus access road that is open to or generally used by the public. 3 "Exceptions: "1. A permit is not required for authorized employees of the City of Paris to use or operate fire hydrants or valves in performance of their duties. "2. A fire permit is not required for a `meter on a fire hydrant' that is installed in accordance with a building arrangement through the City of Paris Water Billing Department and /or the Lamar County Water Supply District. The Fire Code Official shall be notified of all meters installed on fire hydrants." Section 105.6.24, Hot work operations, shall be amended to read as follows: "105.6.24 Hot work operations. An operational permit is required for hot work during public exhibitions and demonstrations." Section 105.6.32, Open burning, shall be amended to read as follows: "105.6.32 Open burning. An operational permit is required to kindle or maintain any fire defined as `open burning' in the city limits of the City of Paris, Texas, with the exception of a "Training Fire" as defined by Section 302.1. "1. Agricultural Burn Permits shall be issued by the Fire Code Official for property that is a minimum of ten acres in size and is zoned agricultural by the City of Paris. An agricultural burn permit will be valid for one (1) full year, and there shall be no fee charged for its issuance. Only brush, limbs, trees and other natural vegetation may be burned at the discretion of the Fire Code Official as long as such material is generated only from that property on which it is to be burned. "2. Standard Burn Permits shall be issued by the Fire Code Official for disposal and recreational fires. Only brush, limbs, trees and clean, untreated lumber may be burned." Section 105.7, Required construction permits, shall be amended by deleting sections 105.7.2, 105.7.3, 105.7.4, 105.7.5, 105.7.10, 105.7.11, and 105.7.18, and by adding Sec. 105.7.19 as follows: "105.7.19 Electronic access control systems. Construction permits are required for the installation or modification of an electronic access control system, as specified in Chapter 10. A separate construction permit is required for the installation or modification of a fire alarm system that may be connected to the access control system. Maintenance performed in E accordance with this code is not considered a modification and does not require a permit." Section 109.3.3, Prosecution of violations, shall be amended to read as follows: "109.3.3 Prosecution of violations. If the notice of violation is not complied with promptly, the fire code official, his designee, any City of Paris Code Inspector or City of Paris Police Officer is authorized to request the legal counsel of the jurisdiction to institute the appropriate legal proceedings at law and at equity to restrain, correct or abate such violation or to require removal or termination of the unlawful occupancy of a structure in violation of the provisions of this code or of the order or direction made pursuant hereto including but not limited to criminal prosecution as set forth in Section 109.4 herein." Section 109.4, Violation penalties, is amended to read as follows: "109.4 Violation penalties. Any person, firm, partnership, corporation or association who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the Fire Code Official, or of a permit or certificate used under provisions of this code, shall be deemed guilty of a misdemeanor and, upon conviction in the Municipal Court, shall be subject to a fine not to exceed TWO THOUSAND AND N° /loos ($2,000.00) DOLLARS for each offense, and each and every day such violation continues shall be deemed to constitute a separate and distinct violation. Said violations are strict liability offenses. Section 111.4, Failure to comply, shall be amended to read as follows: "111.4 Failure to comply. Any person, who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable for a fine not to exceed TWO THOUSAND AND NO /loos ($2,000.00) DOLLARS for each offense, and each and every day such violation continues shall be deemed to constitute a separate and distinct violation. Said violations are strict liability offenses. Sec 202, General Definitions, is amended to amend or add the following definitions to read as follows: "ADDRESSABLE FIRE DETECTION SYSTEM. Any system capable of providing identification of each individual alarm - initiating device. The identification shall be in plain English and as descriptive as possible to specifically identify the location of the device in alarm. The system shall have 5 the capability of alarm verification." "[B] AMBULATORY CARE FACILITY. Buildings or portions thereof used to provide medical, surgical, psychiatric, nursing, or similar care on a less than 24 -hour basis to persons who are rendered incapable of self - preservation by the services provided. This group may include but not be limited to the following: - Dialysis centers - Procedures involving sedation - Sedation dentistry - Surgery centers - Colonic centers - Psychiatric centers" "ANALOG INTELLIGENT ADDRESSABLE FIRE DETECTION SYSTEM. Any system capable of calculating a change in value by directly measurable quantities (voltage, resistance, etc.) at the sensing point. The physical analog may be conducted at the sensing point or at the main control panel. The system shall be capable of compensating for long -term changes in sensor response while maintaining a constant sensitivity. The compensation shall have a preset point at which a detector maintenance signal shall be transmitted to the control panel. The sensor shall remain capable of detecting and transmitting an alarm while in maintenance alert." "[B] ATRIUM. An opening connecting three or more stories other than enclosed stairways, elevators, hoistways, escalators, plumbing, electrical, air - conditioning or other equipment, which is closed at the top and not defined as a mall. Stories, as used in this definition, do not include balconies within assembly groups or mezzanines that comply with Section 505 of the International Building Code." "BONFIRE. An outdoor fire utilized for ceremonial purposes. Bonfires shall not be any larger than 20 x 20 x 12 feet prior to ignition and the fuel [fire] shall not be constructed to be higher than twelve (12) feet. The Fire Code Official may allow projections to be higher than twelve (12) feet if, in his opinion, the hazard is not increased by allowing such." "[B] DEFEND IN PLACE. A method of emergency response that engages building components and trained staff to provide occupant safety rel during an emergency. Emergency response involves remaining in place, relocating within the building, or both, without evacuating the building." "FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required by the fire code official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department." "FIREWORKS. Any composition or device for the purpose of producing a visible or an audible effect for entertainment purposes by combustion, deflagration, or detonation, and /or activated by ignition with a match or other heat producing device that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. "Fireworks, 1.4G. Small fireworks devices containing restricted amounts of pyrotechnic composition designed primarily to produce visible or audible effects by combustion. Such 1.4G fireworks which comply with the construction, chemical composition and labeling regulations of the DOTn for Fireworks, UN 0336, and the U.S. Consumer Product Safety Commission as set forth in CPSC 16 CFR Parts 1500 and 1507, are not explosive materials for the purpose of this code. "Fireworks, 13G. Large fireworks devices, which are explosive materials, intended for use in fireworks displays and designed to produce audible or visible effects by combustion, deflagration or detonation. Such 13G fireworks include, but are not limited to, firecrackers containing more than 130 milligrams (2 grains) of explosive composition, aerial shells containing more than 40 grams of pyrotechnic composition and other display pieces which exceed the limits for classification as 1.4G fireworks. Such 1.3G fireworks are also describe as Fireworks, UN 0335 by the DOTn." "HIGH -PILED COMBUSTIBLE STORAGE. Storage of combustible materials in closely packed piles or combustible materials on pallets, in racks or on shelves where the top of storage is greater than 12 feet (3658 mm) in height. Where required by the fire code official, high -piled combustible storage also includes certain high- hazard commodities, such as rubber tires, Group A plastics, flammable liquids, idle pallets and similar commodities, where the top of storage is greater than 6 feet (1829 mm) in height. "Any building classified as a group S Occupancy or Speculative Building exceeding 6,000 sq. ft. that has a clear height in excess of 14 feet, 7 making it possible to be used for storage in excess of 12 feet, shall be considered to be high -piled storage. When a specific product cannot be identified, a fire protection system and life safety features shall be installed as for Class IV commodities, to the maximum pile height." "HIGH -RISE BUILDING. A building with an occupied floor located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access." "OPEN BURNING. The burning of materials wherein products of combustion are emitted directly into the ambient air without passing through a stack or chimney from an enclosed chamber. Open burning does not include road flares, smudge pots and similar devices associated with safety or occupational uses typically considered open flames, or use of portable outdoor fireplaces. For the purpose of this definition, a chamber shall be regarded as enclosed when, during the time combustion occurs, only apertures, ducts, stacks, flues or chimneys necessary to provide combustion air and permit the escape of exhaust gas are open. Recreational fires and bonfires are types of open burning." "REPAIR GARAGE. A building, structure or portion thereof used for servicing or repairing motor vehicles. This occupancy shall also include garages involved in minor repair, modification and servicing of motor vehicles for items such as lube changes, inspections, windshield repair or replacement, shocks, minor part replacement, and other such minor repairs." "SELF- SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self- service basis." "STANDBY PERSONNEL. Qualified fire service personnel, approved by the Fire Chief, whose only duty shall be to perform constant patrols of the protected premises and keep watch for fire. When utilized, the number required shall be as directed by the Fire Code Official. Charges for utilization shall be as normally calculated by the jurisdiction." "UPGRADED OR REPLACED FIRE ALARM SYSTEM. A fire alarm system that is upgraded or replaced includes, but is not limited to the following: • Replacing one single board or fire alarm control unit component with a newer model • Installing a new fire alarm control unit in addition to or in place of an existing one • Conversion from a horn system to an emergency voice /alarm communication system • Conversion from a conventional system to one that utilizes addressable or analog devices "The following are not considered an upgrade or replacement: • Firmware updates • Software updates • Replacing boards of the same model with chips utilizing the same or newer firmware" Section 307.1.1, General, shall be amended to read as follows: "307.1.1 Prohibited Open Burning. Open burning shall be prohibited that is offensive or objectionable because of smoke emissions or when atmospheric conditions or local circumstances make such fires hazardous shall be prohibited. "Exception: Prescribed burning for the purpose of reducing the impact of wildland fire when authorized by the fire code official." Section 307.2, Permit required, shall be amended to read as follows: "307.2 Permit required. A permit shall be obtained from the fire code official in accordance with Section 105.6 prior to kindling a fire for recognized silvicultural or range or wildlife management practices, prevention or control of disease or pests, or open burning a bonfire. Application for such approval shall only be presented by and permits issued to the owner of the land upon which the fire is to be kindled. "Examples of state or local law, or regulations referenced elsewhere in this section may include but not be limited to the following: "1. Texas Commission on Environmental Quality (TCEQ) guidelines and /or restrictions. "2. State, County, or Local temporary or permanent bans on open burning. "3. Local written policies as established by the fire code official." Section 307.2, Permit required, shall be amended to add subsection 307.2.2, Restricted outdoor burning, to read as follows: "307.2.2 Restricted outdoor burning. It shall be unlawful for a person to ignite or burn materials when the Fire Code Official or other proper authority has determined a 'No Burn Day. "' 7 Section 307.3, Extinguishment authority, shall be amended to read as follows: "307.3 Extinguishment authority. The fire code official is authorized to order the extinguishment by the permit holder, another person responsible or the fire department of open burning that creates or adds to a hazardous or objectionable situation." Section 307.4, Location, shall be amended to read as follows: "307.4 Location. The location for open burning, which shall be allowed only by permit, shall not be less than 300 feet (91 440 mm) from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet (91440 mm) of any structure. "Exceptions: "1. Fires in approved containers that are not less than 15 feet (4572 mm) from a structure. "2. For recreational fires, the minimum required distance from a structure shall be 25 feet (7620 mm) where the pile size is 3 feet (914 mm) or less in diameter and 2 feet (610 mm) or less in height. "3. For disposal fires, the minimum required distance shall be 150 feet from structures that are under the legal control of the permit holder, provided that such qualifying structures contain no sensitive receptors and have an exterior surface made entirely of noncombustible material. "4. The Fire Code Official may reduce the required distance in circumstances where he deems it safe to do so. This exception does not apply to disposal fires." Section 307.4.1, Bonfires, and Section 307.4.2, Recreational fires, shall be deleted. Section 3074.3, Portable outdoor fireplaces, shall be amended to read as follows: "307.4.3 Portable outdoor fireplaces. Portable outdoor fireplaces shall be used in accordance with the manufacturer's instructions and shall not be operated within 15 feet (3048 mm) of a structure or combustible material. "Exceptions: "1. Portable outdoor fireplaces used at one- and two - family dwellings. 10 "2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system." Section 307.4, Location, shall be amended to add Sections 307.4.4, Permanent Outdoor Firepit, and 3.07.4.5, Trench Burns, as follows: "307.4.4 Permanent Outdoor Firepit. Permanently installed outdoor firepits for recreational fire purposes shall not be installed within 10 feet of a structure or combustible material. "Exception: Permanently installed outdoor fireplaces constructed in accordance with the International Building Code." "307.4.5 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with Section 307.2." Section 3075, Attendance, shall be amended to read as follows: "307.5 Attendance. Open burning, trench burns, bonfires, recreational fires, and use of portable outdoor fireplaces shall be constantly attended until the fire is extinguished. A minimum of one portable fire extinguisher complying with Section 906 with a minimum 4 -A rating or other approved on -site fire - extinguishing equipment, such as dirt, sand, water barrel, garden hose or water truck, shall be available for immediate utilization." Section 308.1.4, Open flame cooking devices, shall be amended to read: "308.1.4 Open -flame Cooking Devices. Open -flame cooking devices, charcoal grills and other similar devices used for cooking, heating or any other purposes shall not be operated located or used on combustible balconies, decks, or within 10 feet (3048 mm) of combustible construction. "Exceptions: "1. One- and two - family dwellings, except that LP -gas containers are limited to a water capacity not greater than 50 pounds (22.68 kg) [nominal 20 pound (9.08 kg) LP -gas capacity] with an aggregate LP -gas capacity not to exceed 100 lbs (5 containers). "2. Where buildings, balconies and decks are protected by an approved automatic sprinkler system, except that LP -gas containers are limited to a water capacity not greater than 50 pounds (22.68 kg) [nominal 20 pound (9.08 kg) LP -gas capacity], with an aggregate LP -gas capacity not to exceed 40 lbs (2 containers). 11 "3. LP -gas cooking devices having LP -gas container with a water capacity not greater than 2 Y2 pounds [nominal 1 pound (0.454 kg) LP -gas capacity]." Section 308.1.6.2, Portable fueled open flame devices, Exception #3, shall be amended to read as follows: "Exceptions: "3. Torches or flame - producing devices in accordance with Section 308.1.3." Section 308.1.6.3, Sky lanterns, shall be amended to read as follows: 308.1.6.3 Sky Lanterns. A person shall not release or cause to be released an untethered unmanned free - floating devices containing an open flame or other heat source, such as but not limited to a sky lantern. Section 311.5, Placards, shall be amended to read as follows: 311.5 Placards. The fire code official is authorized to require marking of any vacant or abandoned buildings or structures determined to be unsafe pursuant to Section 110 of this code relating to structural or interior hazards, as required by Section 311.5.1 through 311.5.5. Section 403.5, Group E Occupancies, shall be amended to read as follows: 403.5 Group E Occupancies. An approved fire safety and evacuation plan in accordance with Section 404 shall be prepared and maintained for Group E occupancies and for buildings containing both a Group E occupancy and an atrium. A diagram depicting two evacuation routes shall be posted in a conspicuous location in each classroom. Group E occupancies shall also comply with Sections 403.5.1 through 403.5.3. Section 404.2.2, Fire Safety Plans, shall be amended by adding Section 404.2.2.4.10 as follows: 4.10 Fire extinguishing system controls. Section 405.4, Time, shall be amended to read: 405.4 Time. The fire code official may require an evacuation drill at 12 any time. Drills shall be held at unexpected times and under varying conditions to simulate the unusual conditions that occur in case of fire. Section 501.4, change to read as follows: 501.4 Timing of Installation. When fire apparatus access roads or a water supply for fire protection is required to be installed for any structure or development, they shall be installed, tested, and approved prior to the time of which construction has progressed beyond completion of the foundation of any structure. Section 503.1.1, Buildings and facilities, shall be amended to read as follows: "503.1.1 Buildings and facilities. Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Except for one- or two - family dwellings, the path of measurement shall be along a minimum of a ten feet (10') wide unobstructed pathway around the external walls of the structure. "Fire lanes provided during the platting process shall be so indicated on the plat. Where fire lanes currently exist, the limits of the fire lane shall be shown on a site plan or plat and placed on permanent file with the Fire Marshal and City Engineer. "No owner or person in charge of any premises served by a fire lane or access easement shall abandon, restrict or close any fire lane or easement without first securing from the City of Paris approval of an amended plat or other acceptable legal instrument showing removal of the fire lane." The "Exceptions" to Section 503.1.1 shall remain as written. Section 503.2.1, Dimensions, shall be amended to read as follows: "503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 14 feet (4267 mm). 13 "Exception: Vertical clearance may be reduced; provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved." Section 503.2.2, Authority, shall be amended to read as follows: "503.2.2 Authority. The fire code official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations or where necessary to meet the public safety objectives of the jurisdiction." Section 503.2.3, Surface, shall be amended to read as follows: "503.2.3 Surface. Fire apparatus access roads shall be designed and maintained to support imposed loads of 80,000 Lbs for fire apparatus and shall be surfaced so as to provide all- weather driving capabilities." Section 503.3, Marking, shall be amended to read as follows: "503.3 Marking. Striping, signs, or other markings, when approved by the fire code official, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Striping, signs and other markings shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. "(1) Striping - Fire apparatus access roads shall be continuously marked by painted lines of red traffic paint six inches (6 ") in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4 ") white letters at 25 feet intervals on the red border markings along both sides of the fire lanes. Where a curb is available, the striping shall be on the vertical face of the curb. "(2) Signs - Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" high. Signs shall be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (6'6 ") above finished grade. Signs shall be spaced not more than fifty feet (50') apart along both sides of the fire lane. Signs may be installed on permanent buildings or walls or as approved by the Fire Chief." Section 503.4, Obstruction of fire apparatus access roads, shall be amended to 14 read as follows: "503.4 Obstruction of Fire Apparatus Access Roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained at all times." Section 505.1, Address identification, shall be amended to read as follows: "505.1 Address Identification. New and existing buildings shall be provided with approved address identification. The address identification shall be legible and placed in a position that is visible from the street or road fronting the property. Address identification characters shall contrast with their background. Address numbers shall be Arabic numbers or alphabetical letters. Numbers shall not be spelled out. Each character shall be not less than 6 inches (152.4 mm) high with a minimum stroke width of 1/2 inch (12.7 mm). Where required by the fire code official, address numbers shall be provided in additional approved locations to facilitate emergency response. Where access is by means of a private road, buildings do not immediately front a street, and /or the building cannot be viewed from the public way, a monument, pole or other sign with approved 6 inch (152.4 mm) height building numerals or addresses and 4 inch (101.6 mm) height suite /apartment numerals of a color contrasting with the background of the building or other approved means shall be used to identify the structure. Numerals or addresses shall be posted on a minimum 20 inch (508 mm) by 30 inch (762 mm) background on border. Address identification shall be maintained. "Exception: R -3 Single Family occupancies shall have approved numerals of a minimum 3 1/2 inches (88.9 mm) in height and a color contrasting with the background clearly visible and legible from the street fronting the property and rear alleyway where such alleyway exists." Section 506.1, Where required, shall be amended to add section 506.1.3, to read as follows: "506.1.3. An approved key box shall be provided on each nonresidential occupancy with a fire alarm system or fire sprinkler system. The key box shall contain keys for each locked doorway within the buildings and each elevator. The keys shall be identified as to the corresponding locks." 15 Section 5074, Water Supply test, is amended to read as follows: "507.4 Water Supply Test Date and Information. The water supply test used for hydraulic calculation of fire protection systems shall be conducted in accordance with NFPA 291 "Recommended Practice for Fire Flow Testing and Marking of Hydrants" and within one year of sprinkler plan submittal. The fire code official shall be notified prior to the water supply test. Water supply tests shall be witnessed by the fire code official, as required The exact location of the static /residual hydrant and the flow hydrant shall be indicated on the design drawings. All fire protection plan submittals shall be accompanied by a hard copy of the waterflow test report, or as approved by the fire code official. The report must indicate the dominant water tank level at the time of the test and the maximum and minimum operating levels of the tank, as well, or identify applicable water supply fluctuation. The licensed contractor must then design the fire protection system based on this fluctuation information, as per the applicable referenced NFPA standard. Reference Section 903.3.5 for additional design requirements." Section 507.5.1, Where required, shall be amended to read as follows: "507.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into or within the City of Paris is more than 400 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on -site fire hydrants and mains shall be provided where required by the Fire Code Official. "507.5.1.2 Protected properties. Fire hydrants required to provide a supplemental water supply for automatic fire protection systems shall be within 100 feet of the fire department connection for such systems. "507.5.1.3 Fire hydrant locations. Fire hydrants shall be located 2 feet to 6 feet back from the curb or fire lane and shall not be located in the bulb of a cul -de- sac." Section 5075.4, Obstruction, shall be amended to read as follows: "507.5.4 Obstruction. Unobstructed access to fire hydrants shall be maintained at all times. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being 16 immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants." Section 509.1, Identification, shall be amended to add Section 509.1.2, Sign Requirements, as follows: "509.1.2 Sign Requirements. Unless more stringent requirements apply, lettering for signs required by this section shall have a minimum height of 2 inches (50.8 mm) when located inside a building and 4 inches (101.6 mm) when located outside, or as approved by the fire code official. The letters shall be of a color that contrasts with the background." In Section 603.3.2.1, Quantity Limits, the Exception shall be amended to read as follows: "Exception: The aggregate capacity limit shall be permitted to be increased to 3,000 gallons (11,356 L) in accordance with all requirements of Chapter 57." Section 603.3.2.2, Restricted use and connection, shall be amended to read as follows: "603.3.2.2 Restricted Use and Connection. Tanks installed in accordance with Section 603.3.2 shall be used only to supply fuel oil to fuel - burning equipment installed in accordance with Section 603.3.2.4. Connections between tanks and equipment supplied by such tanks shall be made using closed piping systems." Section 604, EMERGENCYAND STANDBY POWER SYSTEMS, shall be amended to read as follows: "604.1 General. Emergency power systems and standby power systems required by this code or the International Building Code shall comply with Sections 604.1.1 through 604.1.8. "604.1.1 Stationary Generators. Stationary emergency and standby power generators required by this code shall be listed in accordance with UL 2200. "604.1.2 Installation. Emergency power systems and standby power systems shall be installed in accordance with the International Building Code, NFPA 70, NFPA 110 and NFPA 111. Existing installations shall be maintained in accordance with the original approval, except as specified in Chapter 11." 17 There are no changes to Sections 604.1.3 through 604.1.8. "604.1.9 Critical Operations Power Systems (COPS). For Critical Operations Power Systems necessary to maintain continuous power supply to facilities or parts of facilities that require continuous operation for the reasons of public safety, emergency management, national security, or business continuity, see NFPA 70. "604.2 Where Required. Emergency and standby power systems shall be provided where required by Sections 604.2.1 through 604.2.24 or elsewhere identified in this code or any other referenced code." There are no changes to Sections 604.2.1 through 604.2.3. "604.2.4 Emergency Voice /alarm Communications Systems. Emergency power shall be provided for emergency voice /alarm communications systems in the following occupancies, or as specified elsewhere in this code, as required in Section 907.5.2.2.5. The system shall be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72. "Covered and Open Malls, Section 907.2.20 and 914.2.3 Group A Occupancies, Sections 907.2.1 and 907.5.2.2.4. Special Amusement Buildings, Section 907.2.12.3 High -rise Buildings, Section 907.2.13 Atriums, Section 907.2.14 Deep Underground Buildings, Section 907.2.19" There are no changes to Secs. 604.2.5 through 604.2.11 "604.2.12 Means of Egress Illumination. Emergency power shall be provided for means of egress illumination in accordance with Sections 1008.3 and 1104.5.1. (90 minutes) "604.2.13 Membrane Structures. Emergency power shall be provided for exit signs in temporary tents and membrane structures in accordance with Section 3103.12.6.1. (90 minutes) Standby power shall be provided for auxiliary inflation systems in permanent membrane structures in accordance with Section 2702 of the International Building Code. 4 hours Auxiliary inflation systems shall be provided in temporary air - supported and air - inflated membrane structures in accordance with section 3103.10.4." There are no changes to Sec. 604.2.14. "604.2.15 Smoke Control Systems. Standby power shall be provided for smoke control systems in the following occupancies, or as specified elsewhere in this code, as required in Section 909.11: Covered Mall Building, International Building Code, Section 402.7 Atriums, International Building Code, Section 404.7 Underground Buildings, International Building Code, Section 405.8 Group I -3, International Building Code, Section 408.4.2 Stages, International Building Code, Section 410.3.7.2 Special Amusement Buildings (as applicable to Group A's), International Building Code, Section 411.1 Smoke Protected Seating, Section 1029.6.2.1 "604.1.16 Underground Buildings. Emergency and standby power shall be provided in underground buildings as required in Section 405 of the International Building Code and shall be in accordance with Section 604. "604.2.17 Covered and Open Mall Buildings. Emergency power shall be provided in accordance with Section 907.2.20 and 914.2.3. "604.2.18 Airport Traffic Control Towers. A standby power system shall be provided in airport traffic control towers more than 65 ft. in height. Power shall be provided to the following equipment: "1. Pressurization equipment, mechanical equipment and lighting. "2. Elevator operating equipment. "3. Fire alarm and smoke detection systems. "604.2.19 Smokeproof Enclosures and Stair Pressurization Alternative. Standby power shall be provided for smokeproof enclosures, stair pressurization alternative and associated automatic fire detection systems as required by the International Building Code, Section 909.20.6.2. "604.2.20 Elevator Pressurization. Standby power shall be provided for elevator pressurization system as required by the International Building Code, Section 909.21.5. "604.2.21 Elimination of Smoke Dampers in Shaft Penetrations. Standby power shall be provided when eliminating the smoke dampers in ducts penetrating shafts in accordance with the International Building Code, Section 717.5.3, exception 2.3. 19 "604.2.22 Common Exhaust Systems for Clothes Dryers. Standby power shall be provided for common exhaust systems for clothes dryers located in multistory structures in accordance with the International Mechanical Code, Section 504.10, Item 7. "604.2.23 Hydrogen Cutoff Rooms. Standby power shall be provided for mechanical ventilation and gas detection systems of Hydrogen Cutoff Rooms in accordance with the International Building Code, Section 421.8. "604.2.24 Means of Egress Illumination in Existing Buildings. Emergency power shall be provided for means of egress illumination in accordance with Section 1104.5 when required by the fire code official. (90 minutes in I -2, 60 minutes elsewhere.)" There are no changes to Sections 604.3 through 604.7. "604.8 Energy Time Duration. Unless a time limit is specified by the fire code official, in this chapter or elsewhere in this code, or in any other referenced code or standard, the emergency and standby power system shall be supplied with enough fuel or energy storage capacity for not less than 2- hour full- demand operation of the system. "Exception: Where the system is supplied with natural gas from a utility provider and is approved." Section 609.2, Where required, shall be amended to read as follows: "609.2 Where Required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors, including but not limited to cooking equipment used in fixed, mobile, or temporary concessions, such as trucks, buses, trailers, pavilions, or any form of roofed enclosure, as required by the fire code official. 20 "Exceptions: "1. Tents, as provided for in Chapter 31. "2. A Type I hood shall not be required for an electric cooking appliance where and approved testing agency provides documentation that the appliance effluent contains 5 mg /m3 or less of grease when tested at an exhaust flow rate of 500 cfm (0.236 m3 /s) in accordance with UL 71013. "Additionally, fuel gas and power provided for such cooking appliances shall be interlocked with the extinguishing system, as required by Section 904.12.2. Fuel gas containers and piping /hose shall be properly maintained in good working order and in accordance with all applicable regulations." Section 704.1, Enclosure, shall be amended to read as follows: "704.1 Enclosure. Interior vertical shafts including, but not limited to, stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in accordance with the codes in effect at the time of construction but, regardless of when constructed, not less than as required in Chapter 11. New floor openings in existing buildings shall comply with the International Building Code." Section 807.3, Combustible decorative materials, shall be amended to read as follows: "807.3 Combustible Decorative Materials. In occupancies in Groups A, E, I, and R -1, and dormitories in Group R -2, curtains, draperies, fabric hangings and other similar combustible decorative materials suspended from walls or ceilings shall comply with Section 807.4 and shall not exceed 10 percent of the specific wall or ceiling area to which they are attached." Sections 8075.2.2, Artwork in corridors, and 807.5.2.3. Artwork in classrooms, shall be amended to read as follows: "807.5.2.2 Artwork in Corridors. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling or wall to wall. Curtains, draperies, wall hangings, and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible. "Exception: Corridors protected by an approved automatic sprinkler system 21 installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. "807.5.2.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible." Sections 807.5.5.2, Artwork in corridors, and 807.5.5.3. Artwork in classrooms, shall be amended to read as follows: "807.5.5.2 Artwork in Corridors. Artwork and teaching materials shall be limited on the walls of corridors to not more than 20 percent of the wall area. Such materials shall not be continuous from floor to ceiling or wall to wall. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible. "Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. "807.5.5.3 Artwork in Classrooms. Artwork and teaching materials shall be limited on walls of classrooms to not more than 50 percent of the specific wall area to which they are attached. Curtains, draperies, wall hangings and other decorative material suspended from the walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 807 or be noncombustible." Section 901.6.1, Standards, shall be amended to add Section 901.6.1.1, Standpipe testing, as to read as follows: "901.6.1.1 Standpipe Testing. Building owners /managers must maintain and test standpipe systems as per NFPA 25 requirements. The following additional requirements shall be applied to the testing that is required every 5 years: "1. The piping between the Fire Department Connection (FDC) and the standpipe shall be backflushed when foreign material is present, and also hydrostatically tested for all FDC's on any type of standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 22 "2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the tester shall connect hose from a fire hydrant or portable pumping system (as approved by the fire code official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. Confirm that there are no open hose valves prior to introducing water into a dry standpipe. There is no required pressure criteria at the outlet. Verify that check valves function properly and that there are no closed control valves on the system. "3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. All hose valves shall be exercised. "4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's as required by the fire code official. "5. Upon successful completion of standpipe test, place a blue tag (as per Texas Administrative Code, Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the bottom of each standpipe riser in the building. The tag shall be check - marked as "Fifth Year" for Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. "6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction ire code official) shall be followed. "7. Additionally, records of the testing shall be maintained by the owner and contractor, if applicable, as required by the State Rules mentioned above and NFPA 25. "8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected night time freezing conditions. "9. Contact the fire code official for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this firefighting equipment. All standpipe hose valves must remain in place and be provided with an approved 23 cap and chain when approval is given to remove hose by the fire code official." Section 901.6, Inspection, testing and maintenance, shall be amended by adding Section 901.6.3, False Alarms and Nuisance Alarms, to read as follows:. "901.6.3 False Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be given, signaled or transmitted or caused or permitted to be given, signaled or transmitted in any manner." Section 901.7, Systems out of service, shall be amended to read as follows: "901.7 Systems Out of Service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. "Where utilized, fire watches shall be provided with not less than one approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and to keep watch for fires." Section 901.8.2, Removal of existing occupant -use hose lines, shall be amended to read as follows: "901.8.2 Removal of Occupant -use Hose Lines. The fire code official is authorized to permit the removal of occupant -use hose lines and hose valves where all of the following conditions exist: "1. The hose line(s) would not be utilized by trained personnel or the fire department. "2. If the occupant -use hose lines are removed, but the hose valves are required to remain as per the fire code official, such shall be compatible with local fire department fittings." Section 903.1.1, Alternative protection, shall be amended to read as follows: "903.1.1 Alternative Protection. Alternative automatic fire - extinguishing systems complying with Section 904 shall be permitted in addition to automatic sprinkler protection where recognized by the applicable standard, or as approved by the fire code official." 24 Section 903.2, Where required, shall be amended to read as follows and to delete the exception: "903.2 Where required. Approved automatic sprinkler systems in new buildings and structures shall be provided in the locations described in Sections 903.2.1 through 903.2.12. "Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, and elevator hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances. Storage shall not be allowed within the elevator machine room. Signage shall be provided at the entry doors to the elevator machine room indicating `ELEVATOR MACHINERY - NO STORAGE ALLOWED. "' Section 903.2.9, Group S -1, shall be amended by adding Section 903.2.9.3, Self - service storage facility, to read as follows: "903.2.9.3 Self- Service Storage Facility. An automatic sprinkler system shall be installed throughout all self- service storage facilities." Section 903.2.11, Specific buildings areas and hazards, shall be amended by amending Section 903.2.11.3 and by adding Sections 903.2.11.7, 903.2.11.8, and 903.2.11.9 to read as follows: "903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed throughout buildings that have one or more stories, other than penthouses in compliance with Section 1510 of the International Building Code, located 35 feet (10 668 mm) or more above the lowest level of fire department vehicle access, measured to the finished floor. "Exception: Open parking structures in compliance with Section 406.5 of the International Building Code, having no other occupancies above the subject garage." Sections 903.2.11.4- 903.2.11.6 remain unchanged. "903.2.11.7 High -Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm), see Chapter 32 to determine if those provisions apply. "903.2.11.8 Spray Booths and Rooms. New and existing spray booths and spraying rooms shall be protected by an approved automatic fire - extinguishing system. 25 "903.2.11.9 Buildings Over 6,000 sq. ft. An automatic sprinkler system shall be installed throughout all buildings with a building area 6,000 sq. ft. or greater and in all existing buildings that are enlarged to be 6,000 sq. ft. or greater. For the purpose of this provision, fire walls shall not define separate buildings. "Exception: Open parking garages in compliance with Section 406.5 of the International Building Code." Section 903.3.1.1.1, Exempt locations, shall be amended to read as follows: follows: "903.3.1.1.1 Exempt Locations. When approved by the fire code official, automatic sprinklers shall not be required in the following rooms or areas where such rooms or areas are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from a room merely because it is damp, of fire - resistance -rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. "2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the code official. "3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor /ceiling or roof /ceiling assemblies having a fire - resistance rating of not less than 2 hours. "4. Elevator machine rooms, machinery spaces, and hoistways, other than pits where such sprinklers would not necessitate shunt trip requirements under any circumstances." Section 903.3.1.2., NFPA 13R sprinkler systems, shall be amended to add Section 9.3.1.2.3, Attics and attached garages, to read as follows:; add section to read as follows: "[F] Section 903.3.1.2.3 Attics and Attached Garages. Sprinkler protection is required in attic spaces of such buildings two or more stories in height, in accordance with NFPA 13 and or NFPA 13R requirements, and attached garages." Section 903.3.1.3, NFPA 13D sprinkler systems, shall be amended to read as follows: 26 "903.3.1.3 NFPA 13D Sprinkler Systems. Automatic sprinkler systems installed in one- and two - family dwellings; Group R -3; Group R -4 Condition 1 and townhouses shall be permitted to be installed throughout in accordance with NFPA 13D or in accordance with state law." Section 903.3., Installation requirements, shall be amended to add Sec. 903.3.1.4, Freeze protection, to read as follows: "903.3.1.4 Freeze protection. Freeze protection systems for automatic fire sprinkler systems shall be in accordance with the requirements of the applicable referenced NFPA standard and this section. "903.3.1.4.1 Attics. Only dry -pipe, preaction, or listed antifreeze automatic fire sprinkler systems shall be allowed to protect attic spaces. `Exception: Wet -pipe fire sprinkler systems shall be allowed to protect non - ventilated attic spaces where: "1. The attic sprinklers are supplied by a separate floor control valve assembly to allow ease of draining the attic system without impairing sprinklers throughout the rest of the building, and "2. Adequate heat shall be provided for freeze protection as per the applicable referenced NFPA standard, and "3. The attic space is a part of the building's thermal, or heat, envelope, such that insulation is provided at the roof deck, rather than at the ceiling level. "903.3.1.4.2 Heat trace /insulation. Heat trace /insulation shall only be allowed where approved by the fire code official for small sections of large diameter water - filled pipe." Section 903.3.5, Water supplies, shall be amended to read as follows: "903.3.5, Water supplies. Water supplies for automatic sprinkler systems shall comply with this section and the standards referenced in Section 903.3.1. The potable water supply shall be protected against backflow in accordance with the requirements of this section and the International Plumbing Code. For connections to public waterworks systems, the water supply test used for design of fire protection systems shall be adjusted to account for seasonal and daily pressure fluctuations based on 27 information from the water supply authority and as approved by the fire code official. "Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every water -based fire protection system shall be designed with a 10 psi safety factor. Reference Section 507.4 for additional design requirements." Section 903.3, Installation requirements, shall be amended by adding Section 903.3.9, Automatic sprinkler system room access, to read as follows: "903.3.9 Automatic sprinkler system room access. The entrance to the riser room or area of fire appurtenances will be labeled." Section 903.4, Sprinkler system supervision and alarms, shall be amended to add a paragraph after the exceptions, to read as follows: "Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering." Section 903.4.2, Alarms, shall be amended to add a second paragraph, to read as follows: "The alarm device required on the exterior of the building shall be a weatherproof horn /strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection." Section 905.2, Installation standard, shall be amended to read as follows: "905.2 Installation Standard. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high /low alarm." Section 905.3, Required Installations, shall be amended to add Section 905.3.9, Buildings exceeding 10,000 sq. ft., and exception to read as follows: "905.3.9 Buildings Exceeding 10,000 sq. ft. In buildings exceeding 10,000 square feet in area per story and where any portion of the building's NM interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access, Class I automatic wet or manual wet standpipes shall be provided. "Exceptions: "1. Automatic dry and semi - automatic dry standpipes are allowed as provided for in NFPA 14. "2. R -2 occupancies of four stories or less in height having no interior corridors.' Section 905.4, Location of Class 1 standpipe hose connections, shall be amended to read as follows: "905.4 Location of Class I standpipe hose connections. Class I standpipe hose connections shall be provided in all of the following locations: "1. In every required exit stairway, a hose connection shall be provided for each story above and below grade plane. Hose connections shall be located at an intermediate landing between stories, unless otherwise approved by the fire code official. "2. On each side of the wall adjacent to the exit opening of a horizontal exit. "Exception: Where floor areas adjacent to a horizontal exit are reachable from an interior exit stairway hose connection by a 30- foot (9244 mm) hose stream nozzle attached to 100 feet (30 480 mm) of hose, a hose connection shall not be required at the horizontal exit. "3. In every exit passageway, at the entrance from the exit passageway to other areas of a building. "Exception: Where floor areas adjacent to an exit passageway are reachable from an exit stairway hose connection by a 30 -foot (9144 mm) hose stream for a nozzle attached to 100 feet (30 480 mm) of hose, a hose connection shall not be required at the entrance from the exit passageway to other areas of the building. "4. In covered mall buildings, adjacent to each exterior public entrance to the mall and adjacent to each entrance from an exit passageway or exit corridor to the mall. In open mall buildings, adjacent to each public entrance to the mall at the perimeter line and adjacent to each entrance from an exit passageway or exit corridor to the mall. WE "5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3 - percent slope), each standpipe shall be provided with a two -way hose connection located to serve the roof or at the highest landing of an exit stairway with stair access to the roof provided in accordance with Section 1011.12. "6. Where the most remote portion of a nonsprinklered floor or story is more than 150 feet (45 720 mm) from a hose connection or the most remote portion of a sprinklered floor or story is more than 200 feet (60 960 mm) from a hose connection, the fire code official is authorized to require that additional hose connections be provided in approved locations. "7. When required by this Chapter, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred feet (200') intervals along major corridors thereafter, or as otherwise approved by the fire code official." Section 905.9, Valve supervision, shall be amended to add a second paragraph after the exceptions to read as follows: "Sprinkler and standpipe system water -flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering." Section 907.1, General, shall be amended to add Section 907.1.4, Design standards, to read as follows: "907.1.4 Design Standards. Where a new fire alarm system is installed, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke detectors shall have analog initiating devices." Section 907.2.1, Group A, shall be amended to read as follows: "907.2.1 Group A. A manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Group A occupancies not separated from one another in accordance with Section 707.1-10 of the International Building Code shall be considered as a single occupancy for the purposes of applying this section. 30 Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. "Exception. Manual fire alarm boxes are not required where the building is equipped throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1 and the occupant notification appliances will activate throughout the notifications upon sprinkler water flow. "Activation of fire alarm notification appliances shall: "1. Cause illumination of the means of egress with light of not less than 1 foot - candle (11 lux) at the walking surface level, and "2. Stop any conflicting or confusing sounds and visual distractions." Section 907.2.3, Group E, shall be amended in part to read as follows: "907.2.3 Group E. A manual fire alarm system that initiates the occupant notification signal utilizing an emergency voice /alarm communication system meeting the requirements of Section 907.5.2.2 and installed in accordance with Section 907.6 shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings, whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. "Exceptions: "1. A manual fire alarm system is not required in Group E occupancies with an occupant load of 50 or less. "1.1 Residential In -Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 or less years of age, see Section 907.2.6.)" There are no changes to the remainder of the exceptions. In Section 907.2.13, High -rise buildings, Exception 3 shall be amended to read as follows: "3. Open air portions of buildings with an occupancy in Group A -5 in accordance with Section 303.1 of the International Building Code; 31 however, this exception does not apply to accessory uses including but not limited to sky boxes, restaurants, and similarly enclosed areas." Section 907.4.2, Manual fire alarm boxes, shall be amended to add Section 907.4.2.7, Type, to read as follows: "907.4.2.7 Type. Manual alarm initiating devices shall be an approved double action type." Section 907.5.2.1, Audible alarms, shall be amended by adding Section 907.5.2.1.3, Water -flow notification, to read as follows: "907.5.2.1.3 Water -flow notification. When required by section 903.4.2, an exterior audible and visible notification device shall be provided on the exterior of the building and shall be located above the Fire Department Connection. The notification device shall operate on a water - flow alarm only, shall be non - silenceable and shall continue to flash after the panel is silenced on the condition the alarm was a water -flow alarm only. The notification device shall be wired from the fire alarm control panel as a latching circuit." Section 907.6.1, Wiring, shall be amended by adding Section 907.6.1.1, Wiring Installation, to read as follows: "907.6.1.1 Wiring Installation. All fire alarm systems shall be installed in such a manner that a failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of other such devices. All signaling line circuits (SLC) shall be installed in such a way that a single open will not interfere with the operation of any addressable devices (Class A). Outgoing and return SLC conductors shall be installed in accordance with NFPA 72 requirements for Class A circuits and shall have a minimum of four feet separation horizontal and one foot vertical between supply and return circuit conductors. The initiating device circuit (IDC) from a signaling line circuit interface device may be wired Class B, provided the distance from the interface device to the initiating device is ten feet or less." Section 907.6.3, Initiating device identification, shall be amended to delete all four Exceptions. Section 907.6.6, Monitoring, shall be amended to read as follows: 32 "907.6.6 Monitoring. Fire alarm systems required by this chapter or by the International Building Code shall be monitored by an approved supervising station in accordance with NFPA 72. [F] See 907.6.3 for the required information transmitted to the supervising station." The Exceptions will remain unchanged. Section 909, SMOKE CONTROL SYSTEMS, shall be amended to add Section 909.22, Stairway or Ramp Pressurization Alternative, to read as follows: "909.22 Stairway or Ramp Pressurization Alternative. Where the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 and the stair pressurization alternative is chosen for compliance with Building Code requirements for a smokeproof enclosure, interior exit stairways or ramps shall be pressurized to a minimum of 0.10 inches of water (25 Pa) and a maximum of 0.35 inches of water (87 Pa) in the shaft relative to the building measured with all interior exit stairway and ramp doors closed under maximum anticipated conditions of stack effect and wind effect. Such systems shall comply with Section 909, including the installation of a separate fire - fighter's smoke control panel as per Section 909.16, and a Smoke Control Permit shall be required from the fire department as per Section 105.7. "909.22.1 Ventilating equipment. The activation of ventilating equipment for the stair or ramp pressurization system shall be by smoke detectors installed at each floor level at an approved location at the entrance to the smokeproof enclosure. When the closing device for the stairway or ramp shaft and vestibule doors is activated by smoke detection or power failure, the mechanical equipment shall activate and operate at the required performance levels. Smoke detectors shall be installed in accordance with Section 907.3. "909.22.1.1 Ventilation Systems. Smokeproof enclosure ventilation systems shall be independent of other building ventilation systems. The equipment, control wiring, power wiring and ductwork shall comply with one of the following: "1. Equipment, control wiring, power wiring and ductwork shall be located exterior to the building and directly connected to the smokeproof enclosure or connected to the smokeproof enclosure by ductwork enclosed by not less than 2 -hour fire barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both. 33 "2. Equipment, control wiring, power wiring and ductwork shall be located within the smokeproof enclosure with intake or exhaust directly from and to the outside or through ductwork enclosed by not less than 2 -hour barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both. "3. Equipment, control wiring, power wiring and ductwork shall be located within the building if separated from the remainder of the building, including other mechanical equipment, by not less than 2 -hour fire barriers constructed in accordance with Section 707 of the Building Code or horizontal assemblies constructed in accordance with Section 711 of the Building Code, or both. "Exceptions: "1. Control wiring and power wiring utilizing a 2 -hour rated cable or cable system. "2. Where encased with not less than 2 inches (51 mm) of concrete. "3. Control wiring and power wiring protected by a listed electrical circuit protective systems with a fire - resistance rating of not less than 2 hours. "909.22.1.2 Standby Power. Mechanical vestibule and stairway and ramp shaft ventilation systems and automatic fire detection systems shall be provided with standby power in accordance with Section 2702 of the Building Code. "909.22.1.3 Acceptance and Testing. Before the mechanical equipment is approved, the system shall be tested in the presence of the fire code official to confirm that the system is operating in compliance with these requirements." Section 910.2, Where required, shall be amended to amend Exceptions 2 and 3 to read as follows: "2. Only manual smoke and heat removal shall be required in areas of buildings equipped with early suppression fast - response (ESFR) sprinklers. Automatic smoke and heat removal is prohibited. "3. Only manual smoke and heat removal shall be required in areas of buildings equipped with control mode special application sprinklers with a response time index of 50(m *S)1 /2 or less that are listed to control a fire in stored commodities with 12 or fewer sprinklers. Automatic smoke and heat removal is prohibited." 34 Section 910.2, Where required, shall be amended to add Subsection 910.2.3, Group H, to read as follows: "910.2.3 Group H. Buildings and portions thereof used as a Group H occupancy as follows: "1. In occupancies classified as Group H -2 or H -3, any of which are more than 15,000 square feet (1394 mz) in single floor area. "Exception: Buildings of noncombustible construction containing only noncombustible materials. "2. In areas of buildings in Group H used for storing Class 2, 3, and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water - reactive materials as required for a high- hazard commodity classification. "Exception: Buildings of noncombustible construction containing only noncombustible materials." Section 910.3, Smoke and heat vents, shall be amended to add Section 910.3.4 to read as follows: "910.3.4 Vent Operation. Smoke and heat vents shall be capable of being operated by approved automatic and manual means. Automatic operation of smoke and heat vents shall conform to the provisions of Sections 910.3.2.1 through 910.3.2.3. "910.3.4.1 Sprinklered buildings. Where installed in buildings equipped with an approved automatic sprinkler system, smoke and heat vents shall be designed to operate automatically. The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees F (approximately 38 degrees Celsius) greater than the temperature rating of the sprinklers installed. "Exception: Manual only systems per Section 910.2. "910.3.4.2 Nonsprinklered Buildings. Where installed in buildings not equipped with an approved automatic sprinkler system, smoke and heat vents shall operate automatically by actuation of a heat - responsive device rated at between 100 °F (56 °C) and 220 °F (122 °C) above ambient. 35 "Exception: Listed gravity- operated drop out vents." Section 910.4.3.1, Makeup air, shall be amended to read as follows: "910.4.3.1 Makeup Air. Makeup air openings shall be provided within 6 feet (1829 mm) of the floor level. Operation of makeup air openings shall be automatic. The minimum gross area of makeup air inlets shall be 8 square feet per 1,000 cubic feet per minute (0.74 m2 per 0.4719 m3 /s) of smoke exhaust." Section 910.4.4, Activation, shall be amended to read as follows: "910.4.4 Activation. The mechanical smoke removal system shall be activated automatically by the automatic sprinkler system or by an approved fire detection system. Individual manual controls shall also be provided. "Exception: Manual only systems per Section 910.2." Section 912.2, Location, shall be amended to add Section 912.2.3, Hydrant Distance, to read as follows: "912.2.3 Hydrant Distance. An approved fire hydrant shall be located within 100 feet of the fire department connection as the fire hose lays along an unobstructed path." Section 913.2.1, Protection of fire pump rooms, shall be amended to read as follows: "'913.2.1 Protection of fire pump rooms. Rooms where fire pumps are located shall be separated from all other areas of the building in accordance with Section 913.2.1 of the International Building Code. When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft. - 8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1. "Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the fire code official. Access keys shall be provided in the key box as required by Section 506.1." 36 Section 914.3. 1.Z Water supply to required fire pumps, shall be amended to read as follows: "914.3.1.2 Water Supply to required fire pumps. In buildings that are more than 120 feet (128 m) in building height, required fire pumps shall be supplied by connections to no fewer than two water mains located in different streets. Separate supply piping shall be provided between each connection to the water main and the pumps. Each connection and the supply piping between the connection and the pumps shall be sized to supply the flow and pressure required for the pumps to operate. "Exception: Two connections to the same main shall be permitted provided the main is valved such that an interruption can be isolated so that the water supply will continue without interruption through no fewer than one of the connections." Section 1006.2.2. Egress based on use, shall be amended to add a new Section 1006.2.2.6, Electrical Rooms, to read as follows: "1006.2.2.6 Electrical Rooms. For electrical rooms, special exiting requirements may apply. Reference the Electrical Code as adopted." Section 1009.1, Accessible means of egress required, shall be amended to add the following Exception 4: "Exceptions: "4. Buildings regulated under State Law and built in accordance with State registered plans, including any variances or waivers granted by the State, shall be deemed to be in compliance with the requirements of Section 1009." Section 1010.1.9.4, Bolt Locks shall be amended to amend Exceptions 3 and 4 to read as follows: "Exceptions: "3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S occupancy, manually operated edge- or surface - mounted bolts are permitted on the inactive leaf. 37 The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. "4. Where a pair of doors serves a Group A, B, F, M or S occupancy, manually operated edge- or surface - mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress capacity requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. Section 1015.8, Window Openings, shall be amended to amend subsection 1 to read as follows: "1. Operable windows where the top of the sill of the opening is located more than 55 (16 764 mm) above the finished grade or other surface below and that are provided with window fall prevention devices that comply with ASTM F 2006." Section 1020.1, Construction, shall be amended by adding Exception 6, to read as follows: "6. In group B occupancies, corridor walls and ceilings need not be of fire - resistive construction within a single tenant space when the space is equipped with approved automatic smoke - detection within the corridor. The actuation of any detector shall activate self- annunciating alarms audible in all areas within the corridor. Smoke detectors shall be connected to an approved automatic fire alarm system where such system is provided." Section 1029.1.1.1, Spaces under Grandstands and Bleachers, shall be deleted in its entirety. Section 1031.2, Reliability, shall be amended to read as follows: "1031.2 Reliability. Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress." Section 1103.3, Existing elevators, shall be amended to read as follows: "1103.3 Existing elevators. Existing elevators, escalators and moving walks shall comply with the requirements of Sections 1103.3.1 and 1103.3.2. Provide emergency signage as required by Section 607.3." Section 1103.5, Sprinkler systems, shall be amended to add Section 1103.5.4, Group A -2 Spray Booths and Rooms, to read as follows: "1103.5.4 Spray Booths and Rooms. Existing spray booths and spray rooms shall be protected by an approved automatic fire - extinguishing system in accordance with Section 2404." Section 1103.7, Fire alarm systems, shall be amended by adding Sections 1103.7.8, Fire Alarm System Design Standards, and 1103.7.8.1, Communication requirements, to read as follows: "1103.7.8 Fire Alarm System Design Standards. Where an existing fire alarm system is upgraded or replaced, the devices shall be addressable. Fire alarm systems utilizing more than 20 smoke and /or heat detectors shall have analog initiating devices. "Exception: Existing systems need not comply unless the total building, or fire alarm system, remodel or expansion exceeds 30% of the building. When cumulative building, or fire alarm system, remodel or expansion initiated after the date of original fire alarm panel installation exceeds 50% of the building, or fire alarm system, the fire alarm system must comply within 18 months of permit application. "1103.7.8.1 Communication requirements. Refer to Section 907.6.6 for applicable requirements." Section 2304.1, Supervision of dispensing, shall be amended to read as follows: "2304.1 Supervision of Dispensing. The dispensing of fuel at motor fuel - dispensing facilities shall be in accordance with the following: "1. Conducted by a qualified attendant; and /or, "2. Shall be under the supervision of a qualified attendant; and /or "3. Shall be an unattended self- service facility in accordance with Section 2304.3. "At any time the qualified attendant of item Number 1 or 2 above is not present, such operations shall be considered as an unattended self - service facility and shall also comply with Section 2304.3." Section 2401.2, Nonapplicability, shall be deleted in its entirety. 39 Table 3206.2, General Fire Protection and Life Safety Requirements, shall be amended to amend footnote j to read as follows: "j. Where storage areas are protected by either early suppression fast response (ESFR) sprinkler systems or control mode special application sprinklers with a response time index of 50 (m • s) 1/2 or less that are listed to control a fire in the stored commodities with 12 or fewer sprinklers, installed in accordance with NFPA 13, manual smoke and heat vents or manually activated engineered mechanical smoke exhaust systems shall be required within these areas." Section 3310.1, Required access, shall be amended to read as follows: "3310.1 Required access. Approved vehicle access for fire fighting shall be provided to all construction or demolition sites. Vehicle access shall be provided to within 100 feet (30 480 mm) of temporary or permanent fire department connections. Vehicle access shall be provided by either temporary or permanent roads, capable of supporting vehicle loading under all weather conditions. Vehicle access shall be maintained until permanent fire apparatus access roads are available. When fire apparatus access roads are required to be installed for any structure or development, they shall be approved prior to the time at which construction has progressed beyond completion of the foundation of any structure. Section 5601.1.3, Fireworks, shall be amended to read as follows, and Subsection 5601.1.3.1, Seizure, shall be added to read as follows: "5601.1.3 Fireworks. The possession, manufacture, storage, sale, handling, and use of fireworks are prohibited. "Exceptions: "1. Only when approved for fireworks displays, storage, and handling of fireworks as allowed in Section 5604 and 5608. "2. The use of fireworks for approved fireworks displays as allowed in Section 5608. "5601.1.3.1 Seizure. The Fire Code Official or his designee, or any peace officer authorized to enforce the Ordinances of the City of Paris, may seize and destroy illegal fireworks prior to a court appearance, and a photograph of such seized and destroyed fireworks will provide sufficient evidence of a violation of Section 3301.1.3 for the Municipal Court." 40 Section 5703.6, Piping Systems, shall be amended to read as follows: "5703.6 Piping Systems. Piping systems, and their component parts, for flammable and combustible liquids shall be in accordance with Sections 5703.6.1 through 5703.6.11. An approved method of secondary containment shall be provided for underground tank and piping systems." Section 5704.2.9.5, Above - ground tanks inside of buildings, shall be amended to read as follows: "5704.2.9.5 Above - ground Tanks Inside of Buildings. Above- ground tanks inside of buildings shall comply with Section 5704.2.9.5.1 through 5704.2.9.5.3. "5704.2.9.5.1 Overfill prevention. Above - ground tanks storing Class I, II and IIIA liquids inside buildings shall be equipped with a device or other means to prevent overflow into the building including, but not limited to: a float valve; a preset meter on the fill line; a valve actuated by the weight of the tank's contents; a low -head pump that is incapable of producing overflow; or a liquid -tight overflow pipe not less than one pipe size larger than the fill pipe and discharging by gravity back to the outside source of liquid or to an approved location. Tanks containing Class IIIB liquids and connected to fuel- burning equipment shall be provided with a means to prevent overflow into buildings in accordance with Section 5704.2.7.5.8 "5704.2.9.5.2 Fill pipe connections. Fill pipe connections for tanks storing Class I, II, and IIIA liquids and Class IIIB liquids connected to fuel - burning equipment shall be in accordance with Section 2704.2.9.7.6. "5704.2.9.5.3 Combustible liquid storage tanks inside of buildings. The maximum aggregate allowable quantity limit shall be 3,000 gallons (11 356 L) of Class II or III combustible liquid for storage in protected aboveground tanks complying with Section 5704.2.9.7 when all of the following conditions are met: "1. The entire 3,000 gallon (11 356 L) quantity shall be stored in protected above - ground tanks; "2. The 3,000 gallon (11 356 L) capacity shall be permitted to be stored in a single tank or multiple smaller tanks; 41 "3. The tanks shall be located in a room protected by an automatic sprinkler system complying with Section 903.3.1.1; and "4. Tanks shall be connected to fuel- burning equipment, including generators, utilizing an approved closed piping system. "The quantity of combustible liquid stored in tanks complying with this section shall not be counted towards the maximum allowable quantity set forth in Table 5003.1.1(1), and such tanks shall not be required to be located in a control area. Such tanks shall not be located more than two stories below grade." Section 5704.2.11.4, Leak prevention, shall be amended to read as follows: "5704.2.11.4 Leak prevention. Leak prevention for underground tanks shall comply with Sections 5704.2.11.4.1 through 5704.2.11.4.3. An approved method of secondary containment shall be provided for underground tank and piping systems." Section 5704.2.11.4.2, Leak detection, shall be amended to read as follows: "5704.2.11.4.2 Leak detection. Underground storage tank systems shall be provided with an approved method of leak detection from any component of the system that is designed and installed in accordance with NFPA 30 and as specified in Section 5704.2.11.4.3." Section 5704.2.11.4, Leak prevention, shall be amending by adding Section 5704.2.11.4.3, Observation wells, to read as follows: "5704.2.11.4.3 Observation wells. Approved sampling tubes of a minimum 4 inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling tube at the corners of the excavation with a minimum of 4 tubes. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required." Section 6103.2.1, Portable containers, shall be amended by adding Section 6103.2.1.8, Jewelry repair, dental labs and similar occupancies, to read as follows: "6103.2.1.8 Jewelry repair, dental labs and similar occupancies. Where natural gas service is not available, portable LP -Gas containers are 42 allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 20 -pound (9.0 kg) water capacity. Aggregate capacity shall not exceed 60 -pound (27.2 kg) water capacity. Each device shall be separated from other containers by a distance of not less than 20 feet." Section 6104.2, Maximum capacity within established limits, shall be amended to add an exception 2 to read as follows: "Exceptions: "2. Except as permitted in Sections 308 and 6104.3.2, LP -gas containers are not permitted in residential areas." Section 6104.3, Container location, shall be amended to add Section 6104.3.3, Spas, pool heaters, and other listed devices, to read as follows: "6104.3.2 Spas, Pool Heaters, and Other Listed Devices. Where natural gas service is not available, an LP -gas container is allowed to be used to supply spa and pool heaters or other listed devices. Such container shall not exceed 250 - gallon water capacity per lot. See Table 6104.3 for location of containers. "Exception: Lots where LP -gas can be off - loaded wholly on the property where the tank is located may install up to 500 gallon above ground or 1,000 gallon underground approved containers." Section 6107.4, Protecting containers from vehicles, shall be amended to read as follows: "6107.4 Protecting Containers from Vehicles. Where exposed to vehicular damage due to proximity to alleys, driveways or parking areas, LP- gas containers, regulators and piping shall be protected in accordance with Section 312." Section 6109.13, Protection of containers, shall be amended to read as follows: "6109.13 Protection of Containers. LP -gas containers shall be stored within a suitable enclosure or otherwise protected against tampering. Vehicle impact protection shall be provided as required by Section 6107.4." Footnote a. to Table B105.2 in Appendix B shall be amended to read as follows: 43 "a. The reduced fire -flow shall be not less than 1,500 gallons per minute." Section 7. That all provisions of the ordinances of the City of Paris, Texas in conflict with the provisions of this ordinance are hereby repealed, and all other provisions of the ordinances of the City of Paris not in conflict with the provisions of this ordinance shall remain in full force and effect. Section B. That the repeal of any ordinance or part of ordinances affected by the enactment of this ordinance shall not be construed as abandoning any action now pending under or by virtue of such ordinance or as discontinuing, abating, modifying, or altering any penalty accruing or to accrue, or as affecting any rights of the municipality under any section or provisions of any ordinance at the time of passage of this ordinance. Section 9. That it is the intention of the City Council of the City of Paris that this ordinance, and every provision hereof, shall be considered severable, and the invalidity or partial invalidity of any section, clause, or provisions of this ordinance shall not affect the validity of any other portion of this ordinance. Section 10. That any person violating any provision of this ordinance shall be guilty of a Misdemeanor, and upon conviction, shall be subject to a fine in accordance with provisions of Sec. 1 -6 of Chapter One of the City of Paris Code of Ordinances, and each and every day's continuance of any violation of the above - enumerated sections shall constitute and be deemed a separate offense. Section 11. Any violation of this ordinance can be enjoined by a suit filed in the name of the City of Paris in a court of competent jurisdiction, and this remedy shall be in addition to any penal provision provided for in this ordinance or in the City Code of Ordinances of the City of Paris, Texas. Section 12. That this ordinance shall become effective from and after its passage and publication as required by law. PASSED AND ADOPTED on this day of .2017. ATTEST: Janice Ellis, City Clerk .. Cleonne Drake, Mayor Pro Tem APPROVED AS TO FORM: Stephanie H. Harris, City Attorney 'KI