21 - Cross Connection Control Program Ordinance - BackflowItem No. 21
Memorandum
TO: Mayor, Mayor Pro Tern and City Council
Grayson Path, City Manager
FROM: Duke McGee, Building Official, Assistant Director of Planning and Community
Development
Michael Smith, Public Works Director
SUBJECT: Cross Connection Control Prograrn Ordinance (Backflow)
DATE: February 26, 2024
BACKGROUND
Cross connections of water supplies are situations when non -potable water connects with potable
water. This can be very dangerous as it can cause series illness, even death. The importance of
having clearly defined procedures for protecting the public drinking water system from cross
connection hazards cannot be overstated. A cl uali ty and understandable Cross Connection Control
.Program is essential for protecting the city's public drinking water system and ismandated at
both the State and Federal level.
STATUS OF ISSUE
Backflow protection for the city is currently established in the city's irrigation ordinance (Section
4.12), the friternational Plumbing Code ([PC chapters 6 & 13), Texas Commission on
Environmental Quality (TCEQ publications RG 206, RG -345, ECA -476, RG -477, & RG -478), and
the EPA's Cross Connection Control Manual; with referenced standards to:
• Recommended Practice for Backflow Prevention and Cross Connection Control (M14),
third edition, from the American Water Works Association
• Manual of Cross. -Connection Control, tenth edition, from the Foundation for Cross
Connection Control and Hydraulic Research
• Guide to Cross Connection Protection Devices and Assemblies: Application and.
Selection, from the American Society of Sanitary .Engineering
While all of these regulation, standards and manuals are in agreement, they are generic in nature
(developed and written for rnultipl e jurisdictions) and do not address specific local enforcement
sm��
or departmental and owner responsibilities. Having multiple regulation sources with generic
terminology makes it challenging for staff to explain responsibility, installation and enforcement
requirements. Furthermore, it creates challenges for contractors as to what to install and service,
as well as makes it difficult for the owners and the general public to understand.
Placing this information in one document while referencing the above listed rules and regulations
will make the process straightforward and streamline the method of cross -connection protection
of our public drinking water system.
This proposed Cross -Connection Control (Backflow) Ordinance:
• Explains the purpose for backflow protection,
• Defines local duties and responsibilities for our Water Purveyor, Building Safety
Department, Installers and Owners,
• Provides for the city's regulatory compliance
• Establishes enforcement procedures,
• Set fines and procedures for violations and
• Provides relief/appeal protocols.
RECOMMENDATION
Staff recommends adoption of an ordinance establishing a cross -connection control program to
help protect the public drinking water system for the City of Paris.
Page 2 of 2
ORDINANCE NO.
AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF PARIS, TEXAS,
AMENDING CHAPTER 4, "BUILDING REGULATIONS," ARTICLE 4.02,
"CONSTRUCTION CODES AND STANDARDS," DIVISION 5, "PLUMBING
CODE" TO ADD SECTION 4.02.124, "CROSS -CONNECTION CONTROL
PROGRAM;" MAKING OTHER FINDINGS AND PROVISIONS RELATED TO
THE SUBJECT; PROVIDING A REPEALER CLAUSE, A SEVERABILITY
CLAUSE, A SAVINGS CLAUSE, A PENALTY CLAUSE; AND DECLARING AN
EFFECTIVE DATE.
WHEREAS, on April 10, 2023, the City Council adopted the 2021 International
Plumbing Code; and
WHEREAS, the city maintains and operates a public water utility and is responsible
for protecting the integrity and safety of the public water supply; and
WHEREAS, the City Council has determined that state and federal law require
additional regulations related to cross -connection and backflow controls so as to further
protect the public water supply; and
WHEREAS, the City Council has found that the regulations set forth in this ordinance
are in the best interest of the citizens of the city;
NOW, THEREFORE, BE IT RESOLVED BY THE CITY COUNCIL OF THE CITY OF
PARIS, TEXAS:
Section 1. That the findings set out in the preamble to this ordinance are hereby in
all things approved and are incorporated herein by reference for all purposes.
Section 2. That Chapter 4, "Building Regulations," Article 4.02, "Construction
Codes and Standards," Division 4, "Plumbing Code," shall be and is hereby amended by
adding Section 4.02.124, "Cross -Connection Control Program" as set forth in Exhibit A
hereto, which is incorporated by reference as if fully set forth herein.
Section 3. That all provisions of the ordinances of the City of Paris, Texas in conflict
with the provisions of this ordinance are hereby repealed, and all other provisions of the
ordinances of the City of Paris not in conflict with the provisions of this ordinance shall
remain in full force and effect.
Section 4. That the repeal of any ordinance or part of ordinances affected by the
enactment of this ordinance shall not be construed as abandoning any action now pending
under or by virtue of such ordinance or as discontinuing, abating, modifying, or altering any
1
penalty accruing or to accrue, or as affecting any rights of the municipality under any section
or provisions of any ordinance at the time of passage of this ordinance.
Section 5. That it is the intention of the City Council of the City of Paris that this
ordinance, and every provision hereof, shall be considered severable, and the invalidity or
partial invalidity of any section, clause, or provisions of this ordinance shall not affect the
validity of any other portion of this ordinance.
Section 6. That any person violating any provision of this ordinance shall be guilty
of a Misdemeanor, and upon conviction, shall be subject to a fine in accordance with
provisions of Sec. 1.01.009 of the City of Paris Code of Ordinances, and each and every day's
continuance of any violation of the above -enumerated sections shall constitute and be
deemed a separate offense.
Section 7. That this ordinance shall become effective from and after its passage and
publication as required by law.
PASSED AND ADOPTED this 26th day of February, 2024.
Reginald B Hughes, Mayor
ATTEST:
Janice Ellis, City Clerk
APPROVED AS TO FORM:
Stephanie H. Harris, City Attorney
EXHIBIT A
§ 4.02.124 Cross -Connection Control Program
a. Definitions
(1) 290 Rules: The TCEQ's rules and regulations for public water systems, which appear in Title 30,
Texas Administrative Code, Chapter 290.
(2) Auxiliary Water Supply: Any water supply, on or available, to the premises other than the
purveyor's approved public potable water supply.
(3) Backflow: Any unwanted flow of used or nonpotable water, or other substances from any
domestic, industrial, or institutional piping system back into the potable water distribution
system.
(4) Backflow Preventer: A device or means designed to prevent backflow or backsiphonage. Most
commonly categorized as airgap, reduced pressure principle device, double checkvalve assembly,
pressure vacuum breaker, atmospheric vacuum breaker, hose bibb vacuum breaker, residential
dual check, double check with intermediate atmospheric vent, and barometric loop.
L Air Gap: A physical separation sufficient to prevent backflow between the free-flowing
discharge end of the potable water system and any other system. Physically defined as a
distance equal to twice the diameter of the supply side pipe diameter but never less than one
(1) inch.
ii. Atmospheric Vacuum Breaker: A device which prevents backsiphonage by creating an
atmospheric vent when there is either a negative pressure or subatmospheric pressure in a
water system.
iii. Barometric Loop: A fabricated piping arrangement rising at least thirty-five (35) feet at its
topmost point above the highest fixture it supplies. It is utilized in water supply systems to
protect against backsiphonage.
iv. Double Check Valve Assembly: An assembly of two (2) independently operating spring loaded
check valves with tightly closing shut off valves on each side of the check valves, plus properly
located test cocks for the testing of each check valve.
v. Double Check Valve with Intermediate Atmospheric Vent: A device having two (2) spring
loaded check valves separated by an atmospheric vent chamber.
vi. Hose Bibb Vacuum Breaker: A device which is permanently attached to a hose bibb and which
acts as an atmospheric vacuum breaker.
vii. Pressure Vacuum Breaker: A device containing one or two independently operated spring
loaded check valves and an independently operated spring loaded air inlet valve located on
the discharge side of the check or checks. Device includes tightly closing shut-off valves on
each side of the check valves and properly located test cocks for the testing of the check
valve(s).
viii. Reduced Pressure Principle Backflow Preventer: An assembly consisting of two (2)
independently operating approved check valves with an automatically operating differential
relief valve located between the two (2) check valves, tightly closing shut-off valves on each
side of the check valves plus properly located test cocks for the testing of the check valves
and the relief valve.
ix. Residential Dual Check: An assembly of two (2) spring loaded, independently operating check
valves without tightly closing shut-off valves and test cocks. Generally employed immediately
downstream of the water meter to act as a containment device.
(5) Backpressure: Pressure that can cause backflow to occur when a potable system is connected to
a nonpotable supply operating under a higher pressure than the distribution system by means of
a pump, boiler, elevation difference, air or steam pressure, or other means
(6) Backsiphonage: The flow of water or other liquids, mixtures or substances into the distribution
pipes of a potable water supply system from any source other than its intended source caused by
the sudden reduction of pressure in the potable water supply system.
(7) Building Safety Department: The Building Safety Department has the duty and power to enforce
all ordinances and laws regulating construction on private property by providing services such as
permit issuance, plan examination and inspection. The mission of the Building Safety Department
is to protect the lives and safety of the residents and visitors of the City of Paris, preserve quality
of life and contribute to economic development and viability of the community.
(8) Compliance Engine: The Compliance Engine is a web -based service used by the City of Paris to
track and maintain code compliance, reduce false alarm activity, and provide safer communities
through third party inspection reporting and maintenance.
(9) Cross -Connection: A point in a plumbing system where it is possible for a nonpotable substance
to come into contact with the potable drinking water supply. Any actual or potential connection
between the public water supply and a source of contamination or pollution.
(10)Manual M14: The American Water Works Association's Recommended Practice for Backflow
Prevention and Cross -Connection Control, current edition.
(11)TCEQ: The Texas Commission on Environmental Quality.
(12)Water Purveyor: The Water Purveyor has the responsibility to supply potable water to the city's
customers and has the authority to take or cause to be taken the necessary measures to ensure
the public drinking water distribution system is protected from any actual or potential backflow
hazards.
(13)Water Service Entrance: That point in the owner's water system beyond the sanitary control of
the water purveyor; generally considered to be the outlet end of the water meter and always
before any unprotected branch.
b. Purpose
Within distribution systems there exist points called cross -connections where nonpotable water
can be connected to potable sources. These cross -connections can provide a pathway for
backflow of nonpotable water into potable sources. Backflow can occur either because of reduced
pressure in the distribution system (termed backsiphonage) or the presence of increased pressure
from a nonpotable source (termed backpressure). Backsiphonage may be caused by a variety of
circumstances, such as main breaks, flushing, pump failure, or emergency firefighting water
drawdown. Backpressure may occur when heating/cooling, waste disposal, or industrial
manufacturing systems are connected to potable supplies and the pressure in the external system
exceeds the pressure in the distribution system. Both situations act to change the direction of
water, which normally flows from the distribution system to the customer, so that nonpotable
and potentially contaminated water from industrial, commercial, or residential sites flows back
into the distribution system through a cross -connection. During incidents of backflow, these
chemical and biological contaminants have caused illness and deaths, with contamination
affecting a number of service connections. In order to protect the life, health and well-being of
the citizens of and visitors to the City of Paris the following Cross -Connection Control Program has
been established.
c. General
(1) No water -service connection shall be made to any establishment where a potential or actual
contamination hazard exists unless the water supply is protected in accordance with the 290 Rules
and this ordinance. No water -service connection shall be made without a release authorization
from the Building Safety Department, and as directed by the Building Official or Plumbing
Inspector, the water purveyor shall discontinue water service if a required air gap or backflow
prevention assembly is not installed, maintained, and tested in accordance with the 290 Rules and
this ordinance.
(2) All residences, building, structures orfacilities that use an auxiliary water supply, such as a private
well, a rainwater -harvesting system, or pump water directly from any impounded water source
or any water supply other than potable water supplied by the City of Paris distribution system,
must install an RPZ at the meter connection or provide an air gap.
(3) No backflow protection at the water service meter is required where an adequate internal cross -
connection control program is in place provided that the cross -connection control program is
documented by a State of Texas licensed Master Plumber or Water -Supply -Protection Specialists.
d. Requirements
(1) On new installations, the Building Safety Department will review owner provided plans, which
shall be completed by a Professional Engineer or Licensed Master Plumber. Upon approval of
plans the Building Safety Department will issue a permit, and perform inspections. In any case, a
minimum of a dual check valve will be required in any new residential construction. Before
Plumbing Final will be approved, device shall be tested by an approved third -party backflow tester
and register with The Compliance Engine.
(2) For premises existing prior to the start of this program, the Building Safety Department will
perform evaluations and inspections of plans and/or premises and inform the owner by letter of
any corrective action deemed necessary, the method of achieving the correction, and the time
allowed for the correction to be made. Ordinarily, ninety (90) days will be allowed, however, this
time period may be shortened depending upon the degree of hazard involved and the history of
the device(s) in question.
(3) The Building Safety Department will not allow any cross -connection to remain unless it is
protected by an approved backflow preventer device for which a permit has been issued and the
device registered with The Compliance Engine, the city's electronic reporting system, and
regularly tested to insure satisfactory operation.
(4) The Building Safety Department shall inform the Owner by letter, of any failure to comply, by the
time of the first re -inspection. The Building Safety Department will allow an additional fifteen (15)
days for the correction. In the event the Owner fails to comply with the necessary correction by
the time of the second re -inspection, the Building Safety Department will inform the Owner by
letter, that the water service to the Owner's premises will be terminated within a period not to
exceed five (5) days. In the event that the Owner informs the Building Safety Department of
extenuating circumstances as to why the correction has not been made, a time extension may be
granted by the Department but in no case will exceed an additional thirty (30) days.
(5) If the Water Purveyor or Plumbing Inspector determines at any time that a serious threat to the
public health exists, the water service will be terminated immediately.
(6) The Building Safety Department shall have on file, a list of Private Contractors who are certified
backflow device testers. All charges for these tests will be paid by the Owner of the building or
property.
e. Owner Responsibility
(1) The property Owner shall be responsible for the elimination or protection of all cross -connections
on his or her premises.
(2) The Owner, after having been informed by a letter from the Building Safety Department, shall at
his expense, install, maintain, and test, or have tested, any and all backflow preventers on his
premises.
(3) The Owner shall correct any malfunction of the backflow preventer which is revealed by periodic
testing.
(4) The Owner shall inform the Building Safety Department of any proposed or modified cross -
connections and also any existing cross connections of which the Owner is aware but may not
have been found by the Building Safety Department.
(5) The Owner shall not install a bypass around any backflow preventer unless there is a backflow
preventer of the same type on the bypass. Owners who cannot shut down operation for testing
of the device(s) must supply additional devices necessary to allow testing to take place.
(6) The Owner shall install backflow preventers in a manner approved by the Department
(7) The Owner shall install only approved backflow preventers.
(8) Any Owner having a private well, or other private water source, must have a permit (issued by
the City of Paris) if the well or source is cross -connected to the City of Paris potable water
distribution system. Permission to cross -connect may be denied by the Water Purveyor, or
designated representative.
(9) The Owner may be required to install a backflow preventer at the service entrance if a private
water source is maintained, even if it is not cross -connected to the City's system.
(10)ln the event the Owner installs plumbing to provide potable water for domestic purposes which
is on the supply side of the backflow preventer, such plumbing must have its own backflow
preventer installed.
(10) The Owner shall be responsible for the payment of all fees for permits, annual or semi-annual
device testing, retesting in the case that the device fails to operate correctly, and second re -
inspections for non-compliance.
f. Installation, Testing, and Maintenance of Backflow Prevention Assemblies
(1) All backflow prevention assemblies must be tested upon installation in accordance with the
manufacturer's instructions, Manual M14, or the University of Southern California's Manual of
Cross -Connection Control by a Licensed Backflow Prevention Assembly Tester and certified to be
operating within specifications. Backflow prevention assemblies that are installed to protect
against health hazards must also be tested and certified to be operating within specifications at
least annually by a recognized Backflow Prevention Assembly Tester.
(2) Assemblies must be repaired, overhauled, or replaced whenever the assemblies are found to be
defective. Original forms recording testing, repairs, and overhaul must be kept and submitted to
the City of Paris' City's designated electronic reporting system, through The Compliance Engine
within five working days of the test, repair or overhaul of each backflow prevention assembly.
(3) Backflow prevention assemblies installed on fire suppression systems must be tested by a
backflow prevention assembly tester permanently employed by an approved fireline contractor.
(4) No backflow prevention assembly or device may be removed from use, or relocated, or other
assembly or device substituted for it, without the approval of the City of Paris' Building Safety
Department.
(5) Test results shall be registered and recorded with the City's designated electronic reporting
system. Completed forms shall be uploaded to City of Paris' City's designated electronic reporting
system within 10 days of test results. Test Results shall be kept on file for three (3) years.
(6) Gauges used for backflow prevention assembly testing must be tested for accuracy at least
annually in accordance with the AWWA's Manual M14 or the current edition of the University of
Southern California's Manual of Cross -Connection Control. A copy of the gauge accuracy test
report must be submitted to the City of Paris' Building Safety Department to demonstrate the
gauge has been tested for accuracy.
(7) A recognized backflow prevention assembly tester must hold a current license issued from the
TCEQ and be registered with the City of Paris' Building Safety Department.
g. Reporting of Inspections and Tests
Records of all installations, inspections, tests and maintenance required by this code shall be provided
electronically to The Compliance Engine which is the City's designated electronic reporting system.
Completed records shall be submitted no later than ten (10) days following the applicable Installation,
inspection, test and maintenance. The submitted report shall contain all information required by the City's
designated electronic reporting system.
h. Customer Service Inspections
(1) A customer service inspection must be completed before the provision of continuous water
service to all new construction, on any existing service when the water purveyor has reason to
believe that cross -connections or other contaminant hazards exist, or after any material
improvement, correction, or addition to the private water -distribution facilities.
(2) Only individuals with the following credentials shall be recognized as capable of conducting a
customer service inspection:
L Plumbing inspectors and water -supply -protection specialists that have been licensed by
the Texas State Board of Plumbing Examiners.
ii. Customer service inspectors that have been licensed by the TCEQ.
(3) The customer service inspection must certify that:
L No direct connection between the public drinking water supply and a potential source of
contamination exists. Potential sources of contamination must be isolated from the public
water system by a properly installed air gap or an appropriate backflow prevention
assembly.
ii. No cross -connection between the public water supply and a private water source exists.
Where an actual, properly installed air gap is not maintained between the public water
supply and a private water supply, an approved reduced -pressure -zone backflow
prevention assembly is properly installed and a service agreement exists for annual
inspection and testing by a recognized backflow prevention assembly tester.
iii. No connection exists that allows water to be returned to the public drinking water supply.
iv. No pipe or pipe fitting that contains more than 0.25 percent lead is used for the
installation or repair of plumbing at any connection that supplies water for human use.
v. No solder or flux that contains more than 0.2 percent lead is used for the installation or
repair of plumbing at any connection that provides water for human use.
L Irrigation Systems
(1) Any irrigation system that is connected to a public or private potable water supply must be
connected through a backflow prevention assembly approved by the Texas Commission on
Environmental Quality.
(2) Backflow prevention assemblies installed on irrigation systems that are classified as health
hazards must be tested at least annually.
(3) Backflow prevention assemblies installed on irrigation systems that are not classified as health
hazards must be tested every 2 years or as required by the adopted plumbing code.
j. Appeal
A person may appeal the decision of the director or regulatory authority by making a written request for
appeal to the appeals officer within seven (7) business days of the adverse decision or action. The appeal
hearing shall be conducted no later than seven (7) business days following receipt of the notice of appeal
unless the parties agree to a later date. The appeal shall be conducted by to the Building Board of Appeals.
The decision of the Building Board of Appeals shall be final.
k. Enforcement
A person who violates any provision of this article by performing a prohibited act or by failing to perform
a required act is guilty of a misdemeanor and, upon conviction, shall be punished by a fine of not less than
$500.00 and not more than $2,000.00. Each day that one or more of the provisions in this ordinance is
violated shall constitute a separate offense. If a person is convicted of 2 (two), or more distinct violations
of this ordinance, the Building Safety Department shall, upon due notice to the customer, be authorized
to discontinue water service to the premises where such violations occur. Services discontinued under
such circumstances shall be restored only upon payment of a reconnection charge, hereby established at
$150.00, and any other costs incurred by the City of Paris in discontinuing service. In addition, suitable
assurance must be given to the Building Safety Department that the same action shall not be repeated
while the ordinance is in effect. Compliance with this ordinance may also be sought through injunctive
relief in district court.