Loading...
19 Public Safety Adoption of 2006 IFCCITY COUNCIL AGENDA ITEM BRIEFING SHEET Submittal Date: Originating Department: Presented By: Agenda Item No.: OS/04/09 Council Date: Fire Department Ronnie Grooms, Fire Chief 19. OS/11/09 RECOMMENDED MOTION: Not an action item - first reading. POLICY ISSUE(S): Public safety BACKGROUND: The last fire code the City officially adopted was the 1994 Standard Fire Code. The State of Texas has mandated the use of certain 2003 International Building Codes and staff is in the process of preparing for adoption various 2006 International Building Codes with the first code proposed for adoption being the 2006 International Fire Code (IFC). City staff, including the City Attorney, City Manager, Fire Department, and Bureau Veritas, have spent many hours reviewing the proposed code and resulting changes required in our Code of Ordinances. A summary of the IFC and changes to the Code of Ordinances accompany this briefing sheet. BOARD/COMMISSION RECOMMENDATION: EXHIBITS: Ordinance; Summary of IFC and Changes to Code of Ordinances ACTION: BUDGET INFO: ❑ Financial Report ❑ Minute Order Expense ❑ Department Report ❑ Resolution Budgeted Amt. ❑ Presentation Z Ordinance y'I'D Actual ❑ Public Hearing ❑ Other Acct. Name Acct. Number FISCAL NOTES: REVIEWED AND APPROVED BY: Z Administration Z City Clerk ❑ Community Development ❑ EMS/IT ❑ Finance Z Fire ❑ Municipal Court Z Legal ❑ Library ❑ Police ❑ Eng./Public Works ❑ Utilities City of Paris 1 U ~(~0.1.i6~a p Revised 2/04/08 DRAFT s/11/o9 attorney\ordwork\current\Amend Chpt 12, New Article IV, Fire Prevention 2009 ORDINANCE NO. AN ORDINANCE OF THE CITY COUNCIL OF THE CITY OF PARIS, TEXAS; AMENDING CHAPTER 12 OF THE CODE OF ORDINANCES OF THE CITY OF PARIS, BY REPEALING ARTICLE III, FIRE RESERVE UNIT, SECTIONS 12-51 THROUGH 12-66 AND REPEALING ARTICLE IV, FIRE PREVENTION CODE, SECTIONS 12-86 THROUGH 12-89; ESTABLISHING A NEW ARTICLE III, E111TITLED FIRE CODE; ADOPTING THE 2006 EDITIOIV OF THE INTERNATIONAL FIRE CODE; ESTABLISHING LOCAL AMENDMENTS TO THE 2006 EDITION OF THE INTERNATIONAL FIRE CODE; PROVIDING FOR ENFORCEMENT; MAKING OTHER FINDINGS AND PROVISIONS RELATED TO THE SUBJECT; PROVIDING A REPEALER CLAUSE, A SEVERABILITY CLAUSE, A SAVINGS CLAUSE, A PENALTY CLAUSE; AND PROVIDING FOR AN EFFECTIVE DATE. WHEREAS, for the last 25 years, the City of Paris has followed and enforced the Standard Fire Code developed by the Southern Building Code Congress (SBCC) as it has been amended from time to time; and, WHEREAS, the SBCC Standard Fire Code has become stale and difficult to administer, and the Fire Chief and the Fire Marshal of the Paris Fire Department have reviewed other fire codes available and have determined that the International Fire Code, 2006 Edition, provides the best uniform fire code and regulations for the Ciry of Paris, Texas; and, WHEREAS, the Fire Chief and Fire Marshal of the Paris Fire Department hereby recommend the 2006 International Fire Code as the best uniform fire code to provide uniform guidelines and regulations for the safeguarding of life and property from fire and explosion hazards arising from the storage, handling and use of hazardous substances, materials and devices, and from conditions hazardous to life or property in the occupancy of buildings and premises in the City of Paris, Texas; and, WHEREAS, the City Council deems it to be in the best interest of the City of Paris and its citizens to repeal the existing Fire Prevention Code and to and adopt the 2006 Edition of the International Fire Code as amended with local amendments as set out below; and, WHEREAS, the City Fire Department has not had an active Fire Reserve Unit in the City of Paris for many years and the Fire Chief desires to remove that Article from Chapter 12 of the City of Paris Code of Ordinances to eliminate any confusion among the citizens of Paris. 1 -0 000163 NOW, THEREFORE, BE IT ORDAINED BY THE CITY COUNCIL OF THE CITY OF PARIS, TEXAS, THAT: Section 1. The findings set out in the preamble to this ordinance are hereby in all things approved. Section 2. Article III, Fire Reserve Unit, Sections 12-51 through 12-66, of Chapter 12 of the City of Paris Code of Ordinances be, and hereby is repealed in its entirety. Section 3. Article IV, Fire Prevention Code, Sections 12-86 through 12-89, of Chapter 12 of the City of Paris Code of Ordinances be, and hereby is repealed in its entirety. Section 4. Chapter 12 of the Code of Ordinances of the City of Paris, be and the same is hereby amended by establishing a new Article III, entitled Fire Code, to read in its entirety as follows: "ARTICLE III. FIRE CODE Sec.12-51. Adoption of International Fire Code. There is hereby adopted by the City Council of the City of Paris, Texas, for the purpose of prescribing regulations governing conditions hazardous to life and property, those certain codes knows as the 2006 Edition of the International Fire Code, as amended including Appendices B, D, E, F and G, to the same extent as if such Code were copied verbatim in this Article subject to local amendments as set forth in this Article. Copies of the Codes and the amendments thereto, as referenced herein, are on file in the office of the City Clerk, City of Paris for permanent record and inspection. These copyrighted standards and recommendations are adopted and designated as the official Fire Code of the City of Paris, except to the extent they are in conflict with any controlling Federal or State law. The standards are published by and are available from the International Code Council, Country Club Hills, Illinois. A copy of the 2006 International Fire Code shall be kept in each of the following locations: The Paris City Library, the City Clerk's office, the Paris Fire Marshal's office and the Office of Community Development. Sec.12-52. Definitions. (a) Whenever the word "jurisdiction" is used in the International Fire Code, it shall mean the corporate city limits of the City of Paris, Texas. (b) Whenever the words "Fire Code Official", or "Fire Chief' are used in the International Fire Code, they shall mean the Fire 2 _ 000170 Marshal of the City of Paris Fire Department. (c) Any reference to the "International Building Code" or the "International Existing Building Code" shall mean the Building Code as adopted and amended by the City of Paris, Texas. (d) Definitions of terms in the Fire Code and the Building Code shall be interchangeable. Sec.12-53. Fire Code Amendments. The following local amendments repeal and reenact or add sections to the 2006 International Fire Code for the purpose of consistency with specific past practices. These amendments shall supersede, replace and/or supplement the 2006 International Fire Code as follows: (1) Section 101.1 shall be amended to include the following: Title. These regulations shall be known as the FIRE CODE of the City of Paris, Texas hereinafter referred to as "this Code" (2) Section 102.1 be amended by adding the following subsection: 5. The provisions of this code apply to buildings built under the International Residential Code and International Building Code. (3) Section 102.4 shall be amended to include the following: 102.4 Application of building other codes. The design and construction of new structures shall comply with this code and the Building Codes adopted by the City of Paris, Texas; and any alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the International Building Code, shall be made in accordance therewith. (4) Section 102.6 shall be amended to read as follows: 102.6 Referenced codes and standards. The codes and standards referenced in this Code shall be those that are listed in Chapter 45 and such codes, when specifically adopted, and standards shall be considered part of the requirements of this Code to the prescribed extent of each such reference. Where 3 ~ Q0017~. differences occur between the provisions of this Code and the referenced standards, the provisions of this Code shall apply. Whenever amendments have been adopted to the referenced codes and standards, each reference to said code and standard shall be considered to reference the amendments as well. Any reference to NFPA 70 (National Electrical Code) or the ICC Electrical Code shall mean the Electrical Code as adopted by the City of Paris. (5) Section 105.1.4 shall be added as follows: 105.1.4 Fees. The Fire Code Official shall administer the following charges: (a) Fire Protection Permit $0.03/square foot building, or $50.00, whichever is greater. (b) Re-inspection fees $75.00 per re-inspection. (c) When City Fire Code Official requires third-party Plan Review and inspections, or both Actual Costs + 10% Administration fee to City of Paris. (d) Burn permits a. Standard - per occurrence, per day $50.00 b. Agricultural -(over ten acres), per year no charge. No fees shall be charged for any subsequent plan review of changes, additions, or revisions to plans which plan review was initiated solely by the Fire Code Official, or his designee, for items that the Fire Code Official failed to identify on a previous plan review. (6) Section 105.4 shall be amended by adding a new Section 105.4.7 to read as follows: Section 105.4.7 Third Party Plan Review. The Fire Code Official has the authority to require third-party fire plan review of construction documents. Such third-party plan review shall be at the sole expense of the owner/developer/applicant, plus an additional 10% administrative fee to the City of Paris based on total cost of third-party plan review. 4 ~ ooQi7'~ (7) Section 105.6 shall be amended by deleting the following subsections: 105.6.1, 105.6.2, 105.6.3, 105.6.4, 105.6.5, 105.6.6, 105.6.7, 105.6.8, 105.6.9, 105.6.10, 105.6.11, 105.6.12, 106.6.13, 105.6.17, 105.6.18, 105.6.19, 105.6.20, 105.6.21, 105.6.22, 105.6.24, 105.6.25, 105.6.26, 105.6.27, 105.6.28, 105.6.29, 105.6.31, 105.6.32, 105.6.33, 105.6.34, 105.6.36, 105.6.37, 105.6.38, 105.6.39, 105.6.40, 105.6.41, 105.6.42, 105.6.43, 105.6.44,105.6.45, and 105.6.46. (8) Section 105.6.15 shall be amended to read as follows: 105.6.15 Fire hydrants and valves. An operational permit is required to use or operate fire hydrants or valves intended for fire suppression purposes which are installed on water systems and accessible to a fire apparatus access road that is open to or generally used by the public. Exceptions: (1) A permit is not required for authorized employees of the City of Paris to use or operate fire hydrants of valves in performance of their duties. (2) A fire permit is not required for a"meter on a fire hydrant" that is installed in accordance with a billing arrangement through the City of Paris Water Billing Department. The Fire Code Official shall be notified of all meters installed on fire hydrants. (9) Section 105.6.23 shall be amended to read as follows: Section 105.6.23 Hot work operations. An operational permit is required for hot work during public exhibitions and demonstrations. (10) Section 105.6.30 shall be deleted and a new Section 105.6.30 added to read as follows: Section 105.6.30 Open Burning. An operational permit is to required to kindle or maintain any fire defined as "Open burning" in the city limits of the City of Paris, Texas with the exception of a"Training Fire" as defined by Section 302.1. 5 m 0 OG I 7 fl), Agricultural Burn Permits shall be issued by the Fire Code Official for property that is a minimum of ten acres in size and is zoned agricultural by the City of Paris. An agricultural burn permit will be valid for one (1) full year and there shall be no fee charged for its issuance. Only brush, limbs, trees and other natural vegetation may be burned at the discretion of the Fire Code Official, as long as such material is generated only from that property. 2. Standard Burn Permits shall be issued by the Fire Code Official for disposal and recreational fires. Only brush, limbs, trees, and clean, untreated lumber may be burned. (11) Section 105.7 shall be amended by deleting the following subsections: 105.7.2, 105.7.3, 105.7.5, 105.7.7, 105.7.8, 105.7.13 (12) Section 105.7.14 shall be added to read as follows: 105.7.14 Fire apparatus access road markings. A construction permit is required to apply markings to fire apparatus access roads. (13) Section 106.2.1 shall be added to read as follows: 106.2.1 The Fire Code Official or his designated representative shall inspect all buildings, premises, or portions thereof as often as may be necessary. An initial inspection and one (1) re- inspection shall be made free of charge. If the Fire Code Official or his designee is required to make follow-up inspections after the initial inspection and re-inspection to determine whether a violation or violations observed during the previous inspection have been corrected, a fee shall be charged. The occupant, lessee, or person making use of the building or premises shall pay said fee or fees within thirty (30) days of being billed as a condition to continued lawful occupancy of the building or premises. 6 0 0 017 (14) Section 106.2.2 shall be added to read as follows: 106.2.2 Inspection requests. It shall be the duty of the permit holder or their duly authorized agent to notify the Fire Code Official when work is ready for inspection. It shall be the duty of the permit holder to provide access to and means for inspections of such work that are required by this code. (15) Section 106.2.3 shall be added to read as follows: 106.2.3 Approval required. Work shall not be done beyond the point indicated in each successive inspection without first obtaining the approval of the Fire Code Official. The Fire Code Official, upon notification, shall make the requested inspections and shall either indicate the portion of the construction that is satisfactory as completed, or notify the permit holder or his or her agent wherein the same fails to comply with this code. Any portions that do not comply shall be corrected and such portion shall not be covered or concealed until authorized by the Fire Code Official. (16) Section 109,2,3.1 shall be added to read as follows: 109.2.3.1 Citations. It is the intent of this department to achieve compliance by the traditional means of inspection, notification, granting of reasonable time to comply and re- inspection. However, the Fire Code Official and fire officers who have the discretionary duty to enforce a code or ordinance may issue a notice to appear (citation) for violations of this code. Citations shall be issued only by qualified personnel as designated by the Fire Code Official. (17) Section 109.3 shall be amended to read as follows: 109.3 Violation Penalties. Any person, firm, partnership, corporation or association violating any provision of this article or of any code adopted herein shall be deemed guilty of a misdemeanor and, upon conviction in the Municipal Court, shall be subject to a fine not to exceed TWO THOUSAND AND N0/loos ($2,000.00) DOLLARS for each offense, and each and every day such violation continues shall be deemed to constitute a separate and distinct violation. 7 - 000175 (18) Section 111.4 shall be amended to read as follows: 111.4 Failure to comply. Any person, firm, partnership, corporation or association who shall continue any work after having been served with a stop work order, except such work as that person is directed to perform to remove a violation or unsafe condition, shall be liable for a fine not to exceed TWO THOUSAND AND NO/loos ($2,000.00) DOLLARS for each offense, and each and every day such violation continues shall be deemed to constitute a separate and distinct violation. (19) Section 202 shall be amended to include the following definitions: ADDRESSABLE FIRE DETECTION SYSTEM. Any system capable of providing identification of each individual alarm- initiating device. The identification shall be in plain English and as descriptive as possible to specifically identify the location of the device in alarm. The system shall have the capabiliry of alarm verification. ANALOG INTELLIGENT ADDRESSABLE FIRE DETECTION SYSTEM. Any system capable of calculating a change in value by directly measurable quantities (voltage, resistance, etc.) at the sensing point. The physical analog may be conducted at the sensing point or at the main control panel. The system shall be capable of compensating for long-term changes in sensor response while maintaining a constant sensitivity. The compensation shall have a preset point at which a detector maintenance signal shall be transmitted to the control panel. The sensor shall remain capable of detecting and transmitting an alarm while in maintenance alert. FIRE WATCH. A temporary measure intended to ensure continuous and systematic surveillance of a building or portion thereof by one or more qualified individuals or standby personnel when required by the Fire Code Official, for the purposes of identifying and controlling fire hazards, detecting early signs of unwanted fire, raising an alarm of fire and notifying the fire department. HIGH-RISE BUILDING. A building having any floors used for human occupancy located more than 55 feet (16 764 mm) above the lowest level of fire department vehicle access. 8 .000176 SELF-SERVICE STORAGE FACILITY. Real property designed and used for the purpose of renting or leasing individual storage spaces to customers for the purpose of storing and removing personal property on a self-service basis. STANDBY PERSONNEL. Qualified fire service personnel, approved by the Fire Code Official, whose only duty shall be to perform constant patrols of the protected premises and keep watch for fire. When utilized, the number required shall be as directed by the Fire Code Official. Charges for utilization shall be as normally calculated by the jurisdiction. TWO-WAY HOSE CONNECTION. A fire hose connection having both external 21/z-inch National Hose Standard threads and externall~/z inch National Hose Standard threads. (20) Section 302.1 shall be amended as follows: Add two sentences to the end of the definition of "Bonfire" that reads: Bonfires shall not be any larger than 2400 cubic feet prior to ignition and the fuel shall not be constructed to be higher than 12 feet. The Fire Code Official may allow projections to be higher than 12 feet if, in his opinion, the hazard is not increased by allowing such. Add a sentence to the end of the definition of "Open Burning" that reads: Recreational fires and bonfires are types of open burning. Add the following definition: TRAINING FIRE. A fire conducted by the Paris Fire Department, or other entity as allowed by the Fire Code Official, for the sole purpose of training in the extinguishment of fires. Proper notification must be given to TCEQ in accordance with the Texas Outdoor Burning Rule. (21) Section 307.2 shall be amended to read as follows: 307.2 Permit required. A permit shall be obtained from the Fire Code Official in accordance with Section 105.6 prior to kindling aflre for open burning. Application for such approval 9 R 0OG17 shall only be presented by, and permits issued to, the owner or the owner's authorized representative of the land upon which the fire is to be kindled. The Fire Code Official may revoke any permit that is found not to be in compliance with this section, causing said permit to be null and void and any fees related to the permit shall not be refunded. Permits and permit holders shall also comply with: 1. Texas Commission of Environmental Quality rules and regulations. 2. State or local, temporary or permanent bans on open burning. 3. Local written policies as established by the Fire Code Official. (22) Section 307.2.1 shall be amended to read as follows: 307.2.1 Authorization. All outdoor burning shall be done in accordance with this Code and Texas Outdoor Burning Rule Title 30 Texas Administrative Code (30 TAC) Sections 111.201 through 111.221. If a conflict should arise between this code and the Texas Outdoor Burning Rule Title 30 Texas Administrative Code (30 TAC) Sections 111.201 through 111.221, then the more stringent rule shall apply. Where required by state or local law or regulations, open burning shall only be permitted with prior approval from the state or local air and water quality management authority, provided that all conditions specified in the authorization are followed. (23) Section 307.2.2 shall be added to read as follows: 307.2.2 Restricted Outdoor Burning. It shall be unlawful for a person, firm, or corporation to ignite or burn materials when the Fire Code Official or other proper authority has determined a "No Burn Day". (24) Section 307.4 shall be amended to read as follows: 307.4 Location. The location for open burning shall not be less than 300 feet from any structure, and provisions shall be made to prevent the fire from spreading to within 300 feet of any structure. 10 Exceptions: 1. The minimum required distance shall be 150 feet from structures that are under the legal control of the permit holder, provided that such qualifying structures contain no sensitive receptors and have an exterior surface made entirely of non-combustible material. 2. The Fire Code Official may reduce the required distance in circumstances where he deems is safe to do so. This exception does not apply to disposal fires. (25) Delete Section 307.4.1 and Section 307.4.2. (26) Insert a new Section 307.4.1 that shall read as follows: 307.4.1 Trench Burns. Trench burns shall be conducted in air curtain trenches and in accordance with Section 307.2 and the State requirements for trench burns. (27) Section 307,5 shall be added to read as follows: Section 307.5 Attendance. Open burning, trench fires, bonfires or recreational fires shall be constantly attended until the fire is extinguished with no remaining embers. A minimum of one portable fire extinguisher complying with Section 906 with a minimum 4-A rating or other approved on-site fire- extinguishing equipment, such as dirt, sand, water barrel, garden hose, or water truck, shall be available for immediate utilization. The fire-extinguishing equipment that is available shall be comparable to the size of the fire. (28) Section 308.3.1 shall be amended to read as follows: 308.3.1 Open-flame cooking and heating devices. Open- flame cooking devices, charcoal grills, outdoor fireplaces and other similar devices used for cooking, heating, or any other purpose shall not be located or used on combustible balconies, decks, or within 10 feet of combustible construction. Exceptions: 1. One- and two-family dwellings. 11 ~ 0QC17~ 2. Where buildings, balconies and deck are protected by an approved automatic sprinkler system. (29) Section 308.3.1.1 shall be amended to read as follows: 308.3.1.1 Liquefied-petroleum-gas-fueled cooking devices. When permitted as listed in the exceptions of Section 308.3.1, LP-gas burners having an LP-gas container with a water capacity greater than 32 fluid ounces [nominal 1 pound (0.454 kg) LP-gas capacity] shall not be located on combustible balconies or within 10 feet (3048 mm) of combustible construction. Exceptions: 1. One- and two-family dwellings may have containers with a water capacity not greater than 5 gallons [nominal 21 pound (9.08 kg) LP-gas capacity] with an aggregate capacity not to exceed 1001bs (5 containers). 2. Other residential occupancies where buildings, balconies and decks are protected by an approved automatic sprinkler system, may have containers with a water capacity not greater than 5 gallons [nominal 21 pound (9.08 kg) LP-gas capacity] with an aggregate capacity not to exceed 401bs (2 containers). (30) Insert a new Section 401.3.4 that shall read as follows: 401.3.4 Fire Alarms and Nuisance Alarms. False alarms shall not be given, signaled, or transmitted or caused or permitted to be given, signaled, or transmitted in any manner. (31) Section 408.5,4 shall be amended to read as follows: 408.5.4 Drill frequency. Emergency evacuation drills shall be conducted at least twelve times per year, four times per year on each shift. (32) Section 503.1.1 shall be amended to add the following language to the first paragraph: Except for single- or two-family residences, the 150 feet (150') shall be measured along a ten foot (10') wide unobstructed pathway around the external walls of the structure. The grade 12 0 OUG18G shall not exceed six (6) percent. The provision of this section notwithstanding, fire lanes may be required to be located within thirty (30') feet of a building, if deemed to be reasonably necessary by the Fire Code Official, to enable proper protection of the building. A five (5') foot wide level pathway shall be provided unobstructed through all barriers. A continuous row of parking between the fire lane and the structure shall be considered a barrier. Fire lane and access easements shall be provided to serve all buildings through parking areas, to service entrances of buildings, loading areas and trash collection areas, and other areas deemed necessary to be available to fire and emergency vehicles. The Fire Code Official is authorized to designate additional requirements for fire lanes where the same is reasonably necessary so as to provide access for fire and rescue personnel. Fire lanes provided during the platting process shall be so indicated on the plat as an easement. Where fire lanes are provided and a plat is not required, the limits of the fire lane shall be shown on a site plan and placed on permanent file with the Fire Marshal and City Engineer. No owner or person in charge of any premises served by a fire lane or access easement shall abandon, restrict or close any fire lane or easement without first securing from the City of Paris, approval of an amended plat or other acceptable legal instrument showing the removal of the fire lane. (33) Sec. 503.2.1 shall be amended to read as follows: 503.2.1 Dimensions. Fire apparatus access roads shall have an unobstructed width of not less than 24 feet (7315 mm), except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 14 feet (4,267 mm). Exception: Vertical clearance may be reduced, provided such reduction does not impair access by fire apparatus and approved signs are installed and maintained indicating the established vertical clearance when approved. 13 - 000181 Any such fire lane easement shall either connect both ends to a dedicated street or provide a turnaround having a minimum outer radius of SO feet. If two or more interconnecting lanes are provided, interior radius for that connection shall be required in accordance with the following: For 90 degree or greater turns only 24' fire lane - minimum radius 20' 30' fire lane - minimum radius 10' (34) Section 503.2.2 shall be amended to read as follows: 503.2.2 Authority. The Fire Code Official shall have the authority to require an increase in the minimum access widths and vertical clearances where they are inadequate for fire or rescue operations. (35) Section 503.2.3 shall be amended to read as follows: Sec. 503.2.3 Surface. Fire lanes shall be constructed of an asphalt or concrete surface capable of supporting the imposed loads of a 2-axle, 75,000 lb. fire apparatus. The design shall be based on the geotechnical investigation of the site, but shall meet the stated minimums, as follows. Those portions of the fire lane within sixty feet (60') of the structure to be protected shall be constructed with 6-inch thick, 3000 psi concrete with No. 3 bars spaced 24 inches on centers both ways and with sub- grade to a density not less than 95 percent as determined by TSDHPT Test Method Tex-113. Portions of the fire lane constructed of asphalt shall be ninety-five (95) percent compaction with a 6-inch asphalt stabilized base and 2-inch type D hot mix asphalt concrete, State Highway specification number 292. Whenever forty percent (40%) of existing, non- conforming fire lanes are replaced within a twelve month period, the entire fire lane shall be replaced according to current standards. All fire lanes shall be maintained and kept in a good state of repair at all times by the owner and the City of Paris shall not be responsible for the maintenance thereof. It shall further be the responsibility of the owner to insure that all fire lane markings required by Sec. 503.3 be properly maintained so that they are easily distinguishable by the public. 14 000182 (36) Section 503.3 shall be amended to read as follows: 503.3 Marking. Striping, signs, or other markings, when approved by the Fire Code Official, shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Striping, signs, or other markings shall be maintained in a clean and legible condition at all times and replaced or repaired when necessary to provide adequate visibility. L1) Striping - Fire apparatus access roads shall be continuously marked by painted lines of red traffic paint six inches (6") in width to show the boundaries of the lane. The words "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" shall appear in four inch (4") white letters having a 1" minimum stroke at 25 feet intervals on the red border markings along both sides of the fire lanes. Where a curb is available, the stripping shall be on both the vertical and horizontal faces of the curb. (2) Signs - Signs shall read "NO PARKING FIRE LANE" or "FIRE LANE NO PARKING" and shall be 12" wide and 18" high. Signs shall be painted on a white background with letters and borders in red, using not less than 2" lettering. Signs shall be permanently affixed to a stationary post and the bottom of the sign shall be six feet, six inches (66") above finished grade. Signs shall be spaced not more than fifty feet (50') apart. Signs may be installed on permanent buildings or walls or as approved by the Fire Code Official. (37) Section 503.4 shall be amended to read as follows: 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads shall not be obstructed in any manner, including the parking of vehicles. The owners or operators of vehicles, equipment or materials parked in or obstructing a Fire Lane shall be responsible for such violation. The minimum widths and clearances established in Section 503.2.1 and any area marked as a fire lane as described in Section 503.3 shall be maintained clear at all times. 1. Fire Lane Violations 15 - OdC183 a. A criminal citation may be issued to the owner or operator of a motor vehicle illegally parked or standing in a designated fire lane (citations may be mailed or delivered in person). b. Unoccupied vehicles or other obstructions in the fire lane may be removed or towed at the expense of the registered owner. (38) Section 505.1 shall be amended to read as follows; 505.1 Address numbers. Approved numerals of a minimum 6" height and of a color contrasting with the background designating the address shall be placed on all new and existing buildings or structures in a position as to be plainly visible and legible from the street or road fronting the property and from all rear alleyways / access. Where buildings do not immediately front a street, approved 6" height building numerals or addresses and 3" height suite/apartment numerals of a color contrasting with the background of the building shall be placed on all new and existing buildings and structures. Address numbers shall be Arabic numerals or letters. The minimum stroke width shall be 0.5 inches. Exception: R-3 Single Family occupancies shall have approved numerals of a minimum 3.5 inches in height and a color contrasting with the background, clearly visible and legible from the street fronting the property and rear alleyway where such alleyway exists. (39) Section 505.1.1 shall be added to read as follows: 505.1.1 Utility shut-off identification. Where it is not immediately obvious which utility shut off services a property, or where required by the Fire Code Official, approved numerals of minimum one-inch height and of a color contrasting with the background shall be placed on gas and electrical meters serving all new and existing buildings or structures. 16 ~ 000184 (40) Section 506.1.2 shall be added to read as follows: Section 506.1.2 Key Box. A key box shall be provided on each occupancy with a fire alarm system or fire sprinkler system. The key box shall contain keys for each locked doorway within the building and each elevator. The keys shall be identified as to the corresponding locks. (41) Section 508.3.1 shall be added to read as follows: Section 508.3.1 Private Fire Hydrant Markings. Private Fire Hydrant shall have caps and bonnets painted a color in according with NFPA 291 Section 5.2.1.2 The barrel of the hydrant shall be painted red as to distinguish them from public hydrants. (42) Section 508.5.1 shall be amended as follows: 508.5.1 Where required. Where a portion of the facility or building hereafter constructed or moved into within the City of Paris is more than 500 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the Fire Code Official. 1. PROTECTED PROPERTIES. Fire hydrants required to provide a supplemental water supply for automatic fire protection system shall be within 100 feet of the fire department connection for such systems. 2. FIRE HYDRANT LOCATIONS. Fire hydrants shall be located 2 feet to 6 feet back from the curb or fire lane and shall not be located in the bulb of a cul-de-sac. (43) Section 511 shall be added to read as follows: SECTION 511 EMERGENCY RADIO COMMUNICATIONS 511.1 Signal strength in buildings. In all new and existing buildings in which the type of construction or distance from an operational emergency services antenna or dispatch site does not provide adequate frequency or signal strength, as determined by the Fire Code Official, the building owner shall 17 . 00(1'1$5 be responsible for providing the equipment, installation and maintenance of said equipment in a manner to strengthen the radio signal. The radio signal shall meet the minimum input/output strengths according to the emergency radio system's provider and fire department's communications officer. (44) Section 704.1 shall be amended to read as follows: 704.1 Enclosure. Interior vertical shafts, including but not limited to stairways, elevator hoistways, service and utility shafts, that connect two or more stories of a building shall be enclosed or protected in accordance with the codes in effect at the time of construction but, regardless of when constructed, not less than as specified in Table 704.1. When openings are required to be protected, openings into such shafts shall be maintained self-closing or automatic-closing by smoke detection. Existing fusible-link-type automatic door-closing devices are permitted if the fusible link rating does not exceed 135° F (57° C). (45) Section 807.4.3.2 and Section 807.4.4.2 shall each be amended to add the following exception: Exception: Corridors protected by an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 shall be limited to 50 percent of the wall area. (46) Section 901,5 shall be amended to read as follows: 901.5 Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the Fire Code Official. The Fire Code Official shall be notified before any required acceptance testing. All required tests shall be conducted by and at the expense of the owner or his representative. The Fire Department shall not be held responsible for any damages incurred in such test. Where it is required that the Fire Department witness any such test, such test shall be scheduled 18 m 000186 with a minimum of 48 hour notice to the Fire Code Official or his representative. (47) Section 901.6.1 shall be amended to read as follows: 901.6.1.1 Standpipe Testing. Building owners/managers must utilize a licensed fire protection contractor to test and certify standpipe systems. In addition to the testing and maintenance requirements of NFPA 25 applying to standpipe systems, the following additional requirements shall be applied to the testing that is required every 5 years: 1. The piping between the Fire Department Connection (FDC) and the standpipe shall be hydrostatically tested for all FDC's on any type of standpipe system. Hydrostatic testing shall also be conducted in accordance with NFPA 25 requirements for the different types of standpipe systems. 2. For any manual (dry or wet) standpipe system not having an automatic water supply capable of flowing water through the standpipe, the contractor shall connect hose from a fire hydrant or portable pumping system (as approved by the Fire Code Official) to each FDC, and flow water through the standpipe system to the roof outlet to verify that each inlet connection functions properly. There is no required pressure criteria at the outlet. Verify that check valves function properly and that there are no closed control valves on the system. 3. Any pressure relief, reducing, or control valves shall be tested in accordance with the requirements of NFPA 25. 4. If the FDC is not already provided with approved caps, the contractor shall install such caps for all FDC's. Contact the Fire Code Official for additional information. 5. Upon successful completion of standpipe test, the contractor shall place a blue tag (as per "Texas Administrative Code, Title 28. Insurance, Part I. Texas Department of Insurance, Chapter 34. State Fire Marshal, Subchapter G. Fire Sprinkler Rules, 28 TAC § 34.720. Inspection, Test and Maintenance Service (ITM) Tag") at the bottom of each standpipe riser in the building. An example of this tag is located at the end of this SOP. The tag shall be check-marked as "Fifth Year" for Type of ITM, and the 19 - Q0(jl8 % note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. 6. The contractor shall follow the procedures as required by "Texas Administrative Code, Title 28. Insurance, Part I. Texas Department of Insurance, Chapter 34. State Fire Marshal, Subchapter G. Fire Sprinkler Rules, 28 TAC" with regard to Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required notification of the local Authority Having Jurisdiction (Fire Code Official). 7. Additionally, records of the testing shall be maintained by the owner and contractor, as required by the State Rules mentioned above and NFPA 25. 8. Standpipe system tests where water will be flowed external to the building shall not be conducted during freezing conditions or during the day prior to expected night time freezing conditions. 9. Contact the Fire Code Official for requests to remove existing fire hose from Class II and III standpipe systems where employees are not trained in the utilization of this firefighting equipment. All standpipe hose valves must remain in place and be provided with an approved cap and chain when approval is given to remove hose by the Fire Code Official. (48) Section 901.7 shall be amended to replace the first paragraph as follows: 901.7 Systems out of service. Where a required fire protection system is out of service or in the event of an excessive number of activations, the fire department and the Fire Code Official shall be notified immediately and, where required by the Fire Code Official, the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. (49) Section 902.1 shall be amended to add a sentence to the definition of "Manual dry" under the "STANDPIPES, TYPES OF" definition to read as follows: The system must be supervised as specified in Section 905.2. 20 w 000188 (50) Section 903.1.2 shall be added to read as follows: 903.1.2 Residential systems. The installation of NFPA 13R sprinkler systems is prohibited. Where such reference is found in this code, NFPA 13 sprinkler system materials, design and installation shall be installed instead on NFPA 13R. Sprinkler coverage of voids between floors as required by NFPA 13 may be omitted when replacing a NFPA 13R system. (51) Section 903.2 shall be amended to delete the exception. (52) Section 903.2.8.3 shall be added to read as follows: Section 903.2.8.3 Self-service storage facility. An automatic sprinkler system shall be installed throughout all self-service storage facilities. Exception: One-story self-service storage facilities that have no interior corridors, with a one-hour fire barrier separation wall installed between every storage compartment. (53) Sections 903.2.10.3, 903.2.10.4, 903.2.10.5, 903.2.10.6 and 903.2.10.7 shall be amended to read as follows: 903.2.10.3 Buildings more than 35 feet in height. An automatic sprinkler system shall be installed throughout buildings with a floor level, other than penthouses in compliance with Section 1509 of the International Building Code, that is located 35 feet (10 668mm) or more above the lowest level of fire department vehicle access. Exception: Open parking structures in compliance with Section 406.3 of the International Building Code. 903.2.10.4 High-Piled Combustible Storage. For any building with a clear height exceeding 12 feet (4572 mm), see Chapter 23 to determine if those provisions apply. 903.2.10.5 Spray Booths and Rooms. Spray booths and spraying rooms installed, constructed, or remodeled after the adoption of this code shall be protected by an approved automatic fire-extinguishing system. 21 ~ 000185 (54) Section 903.3.1,Ishall be amended to read as follows: 903.3.1.1 NFPA 13 sprinkler systems. Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section 903.3.1.1.1. In residential occupancies other than one- or two-family dwellings, sprinklers shall be installed in bathrooms of any size. Sprinklers shall not be omitted in any closet with a floor area of more than 10 square feet. (55) Section 903.3.1.1.1 shall be amended, in part, to read as follows: 903.3.1.1.1 Exempt locations. When approved by the Fire Code Official, automatic sprinklers shall not be required in the following rooms or areas where such room or areas are protected with an approved automatic fire detection system in accordance with Section 907.2 that will respond to visible or invisible particles of combustion. Sprinklers shall not be omitted from any room merely because it is damp, of fire- resistance-rated construction or contains electrical equipment. 1. Any room where the application of water, or flame and water, constitutes a serious life or fire hazard. 2. Any room or space where sprinklers are considered undesirable because of the nature of the contents, when approved by the Fire Code Official. 3. Generator and transformer rooms, under the direct control of a public utility, separated from the remainder of the building by walls and floor/ceiling or roof/ceiling assemblies having a fire-resistance rating of not less than 2 hours. (56) Section 903.3.1.2 shall be deleted and a new Section 903.3.1.2 added to read as follows: 903.1.2 Residential systems. The installation of NFPA 13R sprinkler systems is prohibited. Where such reference is found in this code, NFPA 13 sprinkler system materials, design and installation shall be installed instead of NFPA 13R. 22 - OOr19c (57) Section 903.3.5 shall be amended to add a second paragraph to read as follows: Water supply as required for such systems shall be provided in conformance with the supply requirements of the respective standards; however, every fire protection system shall be designed with a 10 psi safety factor. (58) Section 903.3.8 shall be added to read as follows: 903.3.8 Automatic Sprinkler System Room Access. Sprinkler system risers providing protection for buildings with multiple tenant spaces must be located in a ground floor room directly accessible from the exterior. The door must be labeled as the riser room. Buildings with single tenants may access the riser location from the interior of the building. (59) Section 903.4 shall be amended to add a second paragraph after the Exceptions, to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems, except for fire department hose connection valves, shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. (60) Section 903,4.2 shall be amended to add a second paragraph to read as follows: The alarm device required on the exterior of the building shall be a weatherproof horn-strobe notification appliance with a minimum 75 candela strobe rating, installed as close as practicable to the fire department connection. (61) Section 903.6.2 shall be added to read as follows: 903.6.2 Spray booths and rooms. Spray booths and spray rooms installed, constructed, or remodeled after the adoption of this code shall be protected by an approved automatic fire- extinguishing system in accordance with Section 1504. 23 - 0 oei 19 i (62) Section 905.2 shall be amended to read as follows: 905.2 Installation standards. Standpipe systems shall be installed in accordance with this section and NFPA 14. Manual dry standpipe systems shall be supervised with a minimum of 10 psig and a maximum of 40 psig air pressure with a high/low alarm. (63) Section 905.3.8 shall be added to read as follows: 905.3.8 Building Area. In buildings exceeding 10,000 square feet in area per story, Class I automatic wet or manual wet standpipes shall be provided where any portion of the building's interior area is more than 200 feet (60960 mm) of travel, vertically and horizontally, from the nearest point of fire department vehicle access. Exception: Automatic dry and semi-automatic dry standpipes are allowed as provided for in NFPA 14. (64) Section 905.4, su6section 5 shall be amended to read as follows: 5. Where the roof has a slope less than four units vertical in 12 units horizontal (33.3-percent slope), each standpipe shall be provided with a two-way hose connection located either on the roof or at the highest landing of a stairway with stair access to the roof. An additional hose connection shall be provided at the top of the most hydraulically remote standpipe for testing purposes. (65) Section 905.4 shall be amended to add subsection 7 to read as follows: 7. Class I standpipes shall also be required on all occupancies in which the distance f rom accessible points for the Fire Department ingress to any point in the structure exceeds two hundred fifty feet (250') along the route that a fire hose is laid as measured from the fire apparatus access road. When required by this Code, standpipe connections shall be placed adjacent to all required exits to the structure and at two hundred (200') intervals along major corridors thereafter. 24 - 0 0 0 1916-11, (66) Section 905.9 shall be amended to add a second paragraph before the exceptions to read as follows: Sprinkler and standpipe system water-flow detectors shall be provided for each floor tap to the sprinkler system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves in the sprinkler and standpipe systems except for fire department hose connection valves shall be electrically supervised to initiate a supervisory signal at the central station upon tampering. (67) Section 906.1 shall be amended to read as follows: 906.1 Where required. Portable fire extinguishers shall be installed in the following locations: 1. In Group A, B, E, F, H, I, M, R-1, R-2, R-4 and S occupancies. 2. Within 30 feet (9,144 mm) of commercial cooking equipment. 3. In areas where flammable or combustible liquids are stored, used or dispensed. 4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 1415.1. 5. Where required by the sections indicated in Table 906.1. 6. Special-hazard areas, including but not limited to laboratories, computer rooms, and generator rooms where required by the Fire Code Official. (68) Section 907.1.3 shall be added to read as follows: 907.1.3 Design Standards. All alarm systems, new or replacement, serving 20 or more alarm actuating devices shall be addressable fire detection systems. Alarm systems serving more than 40 smoke detectors or more than 100 total alarm activating devices shall be analog intelligent addressable fire detection systems. 25 - 000193 Exception: Existing systems need not comply unless the total building remodel or expansion initiated after the effective date of this code, as adopted, exceeds 30% of the building. When cumulative building remodel or expansion exceeds 50% of the building must comply within 18 months of permit application. (69) Section 907.2.1 shall be amended to read as follows: 907.2.1 Group A. A manual fire alarm system shall be installed in Group A occupancies having an occupant load of 300 or more persons or more than 100 persons above or below the lowest level of exit discharge. Portions of Group E occupancies occupied for assembly purposes shall be provided with a fire alarm system as required for the Group E occupancy. (70) Section 907.2.3 shall be amended to read as follows: 907.2.3 Group E. A manual fire alarm system shall be installed in Group E educational occupancies. When automatic sprinkler systems or smoke detectors are installed, such systems or detectors shall be connected to the building fire alarm system. An approved smoke detection system shall be installed in all new and existing Group E day care occupancies. Unless separated by a minimum of 100' open space, all buildings whether portable buildings or the main building, will be considered one building for alarm occupant load consideration and interconnection of alarm systems. (71) Section 907.2.3 shall be amended to change Exception #1 and add Exception #1.1 to read as follows: 1. Group E educational and day care occupancies with an occupant load of less than 50 when provided with an approved automatic sprinkler system. 1.1 Residential In-Home day care with not more than 12 children may use interconnected single station detectors in all habitable rooms. (For care of more than five children 2 1/2 years of age or less, see Section 907.2.6.) (72) Section 907.2.12 shall be amended to read as follows: 907.2.12 High-rise buildings. Buildings having any floor used 26 m 000194 for human occupancy located more than 55 feet ( 16 764 mm) above the lowest level of fire department vehicle access shall be provided with an automatic fire alarm system and an emergency voice/alarm communications system in accordance with Section 907.2.12.2. (73) Section 907.2.12 Exception #3, shall be amended to read as follows: 3. Buildings with an occupancy in Group A-5 in accordance with Section 303.1 of the International Building Code, when used for open air seating; however, this exception does not apply to accessory uses including, but not limited to, sky boxes, restaurants and similarly enclosed areas. (74) Section 907.4 shall be amended to add a second paragraph to read as follows: Manual alarm actuating devices shall be an approved double action type. (75) Section 907.6.1 shall be added to read as follows: 907.6.1 Installation. All fire alarm systems shall be installed in such a manner that the failure of any single initiating device or single open in an initiating circuit conductor will not interfere with the normal operation of any other such devices. All initiating circuit conductors shall be Class "A" wired with a minimum of six feet separation between supply and return circuit conductors. IDC - Class "A" style - D; SLC Class "A" Style 6; NAC Class "B" Style Y. The IDC from an addressable device used to monitor the status of a suppression system may be wired Class B, Style B, provided the distance from the addressable device is within 10 feet of the suppression system device. (76) Section 907.9.2 shall be amended, in part, to read as follows: 907.9.2 High-rise buildings. In buildings that have any floor used for human occupancy that is located more than 55 feet (16 764 mm) above the lowest level ...{remainder of section unchanged}. (77) Section 907.10.3 shall be added to read as follows: 27 w 0O1.~195 907.10.3 Water-flow Notification. When required by Section 903.4.2, an exterior audible and visible notification device shall be provided on the exterior of the building and shall be located above the Fire Department Connection. The notification device shall operate on a water-flow alarm only, shall be non- silenceable and shall continue to flash after the panel is silenced on the condition the alarm was a water-flow alarm only. The notification device shall be wired from the fire alarm control panel as a latching circuit (78) Section 907.15.1 shall be added to read as follows: 907.15.1. Communication Requirements. All alarms, supervisory and trouble signals shall be transmitted descriptively to the approved central station, remote supervisory station or proprietary supervising station as defined in NFPA 72, with the correct device designation and location or addressable device identification. Alarms shall be not permitted to be transmitted as a General Alarm or Zone condition. (79) Section 910.1 Exception #2 shall be amended to read as follows: 2. Where areas of buildings are equipped with early- suppression, fast-response (ESFR) sprinklers, only manual smoke and heat vents shall be required within these areas. (80) Section 910.2.4 shall be added to read as follows: 910.2.4 Group H. Buildings and portions thereof used as a Group H occupancy as follows: 1. In occupancies classified as Group H-2 or H-3, any of which are more than 15,000 square feet (1394m2) in single floor area. Exceptions: 1. Buildings of noncombustible construction containing only noncombustible materials. 2. In areas of buildings in Group H used for storing Class 2, 3 and 4 liquid and solid oxidizers, Class 1 and unclassified detonable organic peroxides, Class 3 and 4 unstable (reactive) materials, or Class 2 or 3 water-reactive 28 W. 000196 materials as required for a high-hazard commodity classification. 3. Buildings of noncombustible construction containing only noncombustible materials. (81) Table 910.3 shall be amended by changing the title of the first row of the table from "Group F-1 and S-1" to include "Group H" and to read as follows: Group H, F-1, and S-1 (82) Section 910.3.2.2 shall be amended by adding a second paragraph to read as follows: The automatic operating mechanism of the smoke and heat vents shall operate at a temperature rating at least 100 degrees (F) (approximately 38 degrees Celsius) greater than the temperature rating of the sprinklers installed. (83) Section 912.3.1 shall be amended to read as follows: 912.3.1 Locking fire department connection caps. The Fire Code Official is authorized to require locking caps on existing fire department connections for water-based fire protection systems where the responding fire department carries appropriate key wrenches for removal. Locking caps are required on all fire department connections for water-based fire protection systems installed or modified after the adoption of this code. (84) Section 913.1 shall be amended by adding a second paragraph and exception to read as follows: When located on the ground level at an exterior wall, the fire pump room shall be provided with an exterior fire department access door that is not less than 3 ft. in width and 6 ft. - 8 in. in height, regardless of any interior doors that are provided. A key box shall be provided at this door, as required by Section 506.1. Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior wall, the corridor leading to 29 UU(~19 i the fire pump room access from the exterior of the building shall be provided with equivalent fire resistance as that required for the pump room, or as approved by the Fire Code Official. Access keys shall be provided in the key box as required by Section 506.1. (85) Section 1008.1,3.4 criterion #7 shall be added to read as follows: 7. If a full building smoke detection system is not provided, approved smoke detectors shall be provided on both the access and egress sides of doors and in a location approved by the authority having jurisdiction of NFPA 72. Actuation of a smoke detector shall automatically unlock the door. (86) Section 1008.1.3.4 shall be amended to add the following exception: Exception: In Group E Occupancies where ingress is available by keys located in a KEY BOX mounted at the main entrance to the building, the Fire Alarm must unlock the egress portion or capability of all doors while the ingress function may remain locked (87) Section 1017.1 shall be amended to add Exception #5 to read as follows: 5. In Group B office buildings, corridor walls and ceilings need not be of fire-resistive construction within office spaces of a single tenant when the space is equipped with an approved automatic smoke-detection system within the corridor. The actuation of any detector shall activate alarms audible in all areas served by the corridor. The smoke-detection system shall be connected to the building's fire alarm system where such a system is provided. (88) Section 1020.1.7 shall be amended, in part, to read as follows: 1020.1.7 Smokeproof enclosures. In buildings required to comply with Section 403 or 405 of the International Building Code, each of the exits of a building that serves stories where any floor surface is located more than 55 feet (16 764 mm) above the lowest level of fire {remainder of section unchanged}. 30 n 000198 (89) Section 1028.2 shall be amended to read as follows: 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the Fire Code Official. (90) Section 1504.4 shall be amended, in part, to read as follows: 1504.6 Fire Protection. Spray booths and spray rooms installed, constructed , or remodeled after the adoption of this code shall be protected by an approved automatic fire- extinguishing system [remainder of section unchanged} (91) Section 2204.1 shall be amended to read as follows: 2204.1 Supervision of dispensing. The dispensing of fuel at motor fuel-dispensing facilities shall be in accordance with the following: 1. Conducted by a qualified attendant; or, 2. Shall be under the supervision of a qualified attendant; or, 3. Shall be an unattended self-service facility in accordance with Section 2204.3. At any time the qualified attendant of item #1 or #2 above is not present, such operations shall be considered as an Unattended self-service facility and shall also comply with Section 2204.3. (92) Section 2302 shall be amended by adding a second paragraph to the definition of "High-Piled Combustible Storage" to read as follows: Any building exceeding 12,000 sq. ft. that has a clear height in excess of 12 feet, making it possible to be used for storage in excess of 12 feet, shall be considered to be high-piled storage and shall comply with the provisions of this section. When a specific product cannot be identified, a fire protection system shall be installed as for Class IV commodities, to the maximum pile height. 31 - 0U019S (93) Table 2306.2 shall be amended by replacing the text of 'footnote j" to read as follows: Where areas of buildings are equipped with early- suppression, fast-response (ESFR) sprinklers, only manual smoke and heat vents shall be required within these areas. (94) Section 3301.1.3 shall be amended to read as follows: 3301.1.3 Fireworks. The possession, manufacture, storage, sale, handling and use of fireworks are prohibited. Exceptions: 1. Only when approved for fireworks displays, storage and handling of fireworks as allowed in Section 3304 and 3308. 2. The use of fireworks for approved display as allowed in Section 3308. The presence or use of fireworks within the jurisdiction of the City of Paris in violation of this ordinance is hereby declared to be a common and public nuisance. The restrictions of this Section shall be applicable and in force throughout the territory of the City of Paris, Texas. The owner, lessee or occupant of the property or structure where fireworks are being stored or used shall be deemed responsible for violating this section. (95) Section 3301.7.1 shall be added to read as follows: 3301.7.1. The Fire Code Official or his designee, or any peace officer authorized to enforce the Ordinances of the City of Paris, may seize and destroy illegal fireworks prior to a court appearance and a photograph of such seized and destroyed fireworks will provide sufficient evidence of a violation of Section 3301.1.3 for the municipal court. (96) Section 3302 shall be amended, in part, by amending the definition of "fireworks" to read as follows: FIREWORKS. Any composition or device for the purpose of 32 - 000200 producing a visible or an audible effect for entertainment purposes by combustion, deflagration, detonation, and/or activated by ignition with a match or other heat producing device that meets the definition of 1.4G fireworks or 1.3G fireworks as set forth herein. (97) Section 3403.6 shall be amended to add a sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and piping systems. (98) Section 3404.2.11.5 shall be amended to add a sentence to read as follows: An approved method of secondary containment shall be provided for underground tank and piping systems. (99) Section 3404.2,11.5.2 shall be amended to read as follows: 3404.2.11.5.2 Leak detection. Underground storage tank systems shall be provided with an approved method of leak detection from any component of the system that is designed and installed in accordance with NFPA 30 and as specified in Section 3404.2.11.5.3. (100) Section 3404.2.11.5.3 shall be added to read as follows: 3404.2.11.5.3 Dry sumps. Approved sampling tubes of a minimum 6 inches in diameter shall be installed in the backfill material of each underground flammable or combustible liquid storage tank. The tubes shall extend from a point 12 inches below the average grade of the excavation to ground level and shall be provided with suitable surface access caps. Each tank site shall provide a sampling sump at the corners of the excavation with a minimum of 4 sumps. Sampling tubes shall be placed in the product line excavation within 10 feet of the tank excavation and one every 50 feet routed along product lines towards the dispensers, a minimum of two are required. (101) Section 3406.5.4.5 shall be deleted and replaced with the following: 33 - 0OC;20i 3406.5.4.5 Commercial, industrial, governmental or manufacturing. Dispensing of Class II and III motor vehicle fuel from tank vehicles into the fuel tanks of motor vehicles located at commercial, industrial, governmental or manufacturing establishments is allowed where permitted, provided such dispensing operations are conducted in accordance with Sections 3406.5.4.5.1 through 3406.5.4.5.3. 3406.5.4.5.1 Site requirements. 1. Dispensing may occur at sites that have been permitted to conduct mobile fueling. 2. A detailed site plan shall be submitted with each application for a permit. The site plan must indicate: a. all buildings, structures, and appurtenances on site and their use or function; b. all uses adjacent to the property lines of the site; c. the locations of all storm drain openings, adjacent waterways or wetlands; d. information regarding slope, natural drainage, curbing, impounding and how a spill will be retained upon the site property; and, e. The scale of the site plan. 3. The Fire Code Official is authorized to impose limits upon: the times and/or days during which mobile fueling operations are allowed to take place and specific locations on a site where fueling is permitted. 4. Mobile fueling operations shall be conducted in areas not generally accessible to the public. 5. Mobile fueling shall not take place within 15 feet (4.572 m) of buildings, property lines, or combustible storage. 3406.5.4.5.2 Refueling Operator Requirements. 1. The owner of a mobile fueling operation shall provide to the jurisdiction a written response plan which demonstrates readiness to respond to a fuel spill, carry out,appropriate mitigation measures, and to indicate its process to properly dispose of contaminated materials 34 m 000 20 21' when circumstances require. 2. The tank vehicle shall comply with the requirements of NFPA 385 and Local, State and Federal requirements. The tank vehicle's specific functions shall include that of supplying fuel to motor vehicle fuel tanks. The vehicle and all its equipment shall be maintained in good repair. 3. Signs prohibiting smoking or open flames within 25 feet (7.62 m) of the tank vehicle or the point of fueling shall be prominently posted on 3 sides of the vehicle including the back and both sides. 4. A fire extinguisher with a minimum rating of 40:13C shall be provided on the vehicle with signage clearly indicating its location. 5. The dispensing nozzles and hoses shall be of an approved and listed type. 6. The dispensing hose shall not be extended from the reel more than 100 feet (30.48m) in length. 7. Absorbent materials, non-water absorbent pads, a 10 foot (3.048 m) long containment boom, an approved container with lid, and a non-metallic shovel shall be provided to mitigate a minimum 5-gallon fuel spill. 8. Tanker vehicles shall be equipped with a fuel limit switch such as a count-back switch, limiting the amount of a single fueling operation to a maximum of 500 gallons (1893 L) between resettings of the limit switch. Exception: Tankers utilizing remote emergency shut-off device capability where the operator constantly carries the shut-off device which, when activated, immediately causes flow of fuel from the tanker to cease. 9. Persons responsible for dispensing operations shall be trained in the appropriate mitigating actions in the event of a fire, leak, or spill. Training records shall be maintained by the dispensing company and shall be made available to the Fire Code Official upon request. 35 0 0 0 2 nJ 10. Operators of tank vehicles used for mobile fueling operations shall have in their possession at all times an emergency communications device to notify the proper authorities in the event of an emergency. 3406.5.4.5.3 Operational Requirements. 1. The tank vehicle dispensing equipment shall be constantly attended and operated only by designated personnel who are trained to handle and dispense motor fuels. 2. Prior to beginning dispensing operations, precautions shall be taken to assure ignition sources are not present. 3. The engines of vehicles being fueled shall be shut off during dispensing operations. 4. Night time fueling operations shall only take place in adequately lighted areas. 5. The tank vehicle shall be positioned with respect to vehicles being fueled so as to preclude traffic from driving over the delivery hose and between the tank vehicle and the motor vehicle being fueled. 6. During fueling operations, tank vehicle brakes shall be set, chock blocks shall be in place and warning lights shall be in operation. 7. Motor vehicle fuel tanks shall not be topped off. 8. The dispensing hose shall be properly placed on an approved reel or in an approved compartment prior to moving the tank vehicle. 9. The Code Official and other appropriate authorities shall be notified when a reportable spill or unauthorized discharge occurs. (102) Section 3803.2.1.8 shall be added to read as follows: 3803.2.1.8 Jewelry Repair, Dental Labs and Similar Occupancies. Where natural gas service is not available, 36 Q0020~ portable LP-Gas containers are allowed to be used to supply approved torch assemblies or similar appliances. Such containers shall not exceed 21-pound (9.0 kg) LPG capacity. Aggregate capaciry shall not exceed 63-pound (27.2 kg) LPG capacity. Each device shall be separated from other containers by a distance of not less than 20 feet. (103) Section 3804.2 shall be amended to add Exception #2 to read as follows: Exceptions: 2. Except as permitted in 308.3 and 3804.3.2, LP-gas containers are not permitted in residential areas. (104) Section 3804,3.2 shall be added to read as follows: 3804.3.2 Spas, Pool Heaters and other listed devices. Where natural gas service is not available, LP-Gas containers are allowed to be used to supply spa and pool heaters or other listed devices. Such containers shall not exceed 250-gallon water capacity. See Table 3804.3 for location of containers." Section 5. That all provisions of the ordinances of the City of Paris, Texas in conflict with the provisions of this ordinance are hereby repealed, and all other provisions of the ordinances of the City of Paris not in conflict with the provisions of this ordinance shall remain in full force and effect. Section 6. That the repeal of any ordinance or part of ordinances affected by the enactment of this ordinance shall not be construed as abandoning any action now pending under or by virtue of such ordinance or as discontinuing, abating, modifying, or altering any penalty accruing or to accrue, or as affecting any rights of the municipality under any section or provisions of any ordinance at the time of passage of this ordinance. Section 7. That it is the intention of the Ciry Council of the City of Paris that this ordinance, and every provision hereof, shall be considered severable, and the invalidity or partial invalidity of any section, clause, or provisions of this ordinance shall not affect the validity of any other portion of this ordinance. Section 8. That any person violating any provision of this ordinance shall be guilty of a Misdemeanor, and upon conviction, shall be subject to a fine in accordance with provisions of Sec. 1- 6 of Chapter One of the City of Paris Code of Ordinances, and each and every day's continuance of any violation of the above-enumerated sections shall constitute and be deemed a separate offense. 37 2 P) Section 9. Any violation of this ordinance can be enjoined by a suit filed in the name of the City of Paris in a court of competent jurisdiction, and this remedy shall be in addition to any penal provision provided for in this ordinance or in the City Code of Ordinances of the City of Paris, Texas. Section 10. Introduced and read on first reading on May 11, 2009, at a regular meeting of the City Council of the City of Paris and read and passed on second reading on May 26, 2009, at a regular meeting of the City Council of the City of Paris; the same being two (2) separate regular meetings of the City Council of the City of Paris. 1or] Section 10. That by a supermajority vote of _ ayes and nays, the City Council voted to suspend the rule requiring two readings before adoption of this ordinance. Section 11. That this ordinance shall become effective from and after its passage of the second[first] reading and publication as required by law. PASSED AND ADOPTED on second and final reading this 26th day of May, 2009. Jesse James Freelen, Mayor ATTEST: Janice Ellis, City Clerk APPROVED AS TO FORM: Kent McIlyar, City Attorney 38 SUMMARY SHEET SUPPORTING ADOPTION OF THE 2006 INTERNATIONAL FIRE CODES The Paris Fire Department wholeheartedly supports and encourages the City of Paris to formally adopt the 2006 International Fire Code based on the following: The Paris Fire Department recognizes the need for a modern, up-to-date fire code, consistent with nationally recognized good practice, which addresses conditions hazardous to life and property from fire, explosion, handling or use of hazardous materials and the use and occupancy of buildings and premises. 2. Proper utilization of the code will help facilitate a safer environment for firefighters and emergency responders and help safeguard public health and safety. 3. The International Fire Code is designed to meet these needs through model code regulations. 4. The IFC is compatible with all the International Codes published by the International Code Council (ICC) and those provisions of the NFPA. 5. The City currently uses the International Building Code and plans to adopt the 2006 edition at a later date. The IBC specifically references the IFC more than 100 times, therefore, adopting the 2006 IFC will ease confusion and help to make the City's Code Enforcement process more flawless and user friendly. 6. The City of Paris has not updated its Fire Code since last adopting the 1994 Standard Fire Prevention Code (which is out of print). This code is now obsolete and is exceedingly too vague and ambiguous. The IFC will help better define and clarify specifics regarding code requirements and compliance. A major plus for adopting the 2006 IFC, as amended and recommended by the Paris Fire Department, will: Ease unnecessary prohibitions on open burning, the unintended consequences for such burning, and closer reflect or mirror state regulations. 2. Establish a fee schedule whereby the FD can recoup the cost of providing such Fire Prevention service. 0 f % ~i r. 1~ u