Laserfiche WebLink
TEXAS STATE FIRE MARSHAL'S OFFICE <br />y FIRE SAFETY INSPECTION REPORT <br />The following floors do not have exit signs. <br />• Second <br />• Third <br />• Fourth <br />• Fifth <br />• Sixth <br />NFPA 1, Fire Code, Chapter 14.14.1.2.1 <br />VIOLATION 8 <br />There are not emergency lights on the following floors. <br />• First <br />• Second <br />• Third <br />• Fourth <br />• Fifth <br />• Sixth <br />NFPA 1, Fire Code, Chapter 14.13.1.1(3) <br />MEOM—NA101M, <br />Unused wiring or electrical panels shall be removed or identified at its termination. <br />NFPA 1, Fire Code, Chapter 11.1.4 <br />VIOLATION 10 <br />The electrical breaker panels were not identified. <br />NFPA 1, Fire Code, Chapter 11.1.9.3.1 <br />VIOLATION 11 <br />The west side of the building has masonry separation which could cause a collapse of the brick <br />veneer from the wall. <br />NFPA 1, Fire Code, Chapter 10.1.4.1 and 10.1.4.2 <br />VIOLATION 12 <br />Inspection Number RRO15800A Page 3 of 5 <br />Revised 12/2014 <br />