Laserfiche WebLink
0 TEXAS STATE FIRE MARSHAL'S OFFICE <br />'` j FIDE SAFETY INSPECTION REPORT <br />The building does not have the required two hour separation between the assembly and <br />apartment occupancies. <br />NFPA 1, Fire Code, Table 6.1.14.4.1 (a) <br />Note: Once the building is fully sprinkler this requirement may be removed upon review of AHJ. <br />VIOLATION 4 <br />The stairwell doors do not have the required UL Labels for fire rated doors on the following <br />stories. <br />• First <br />• Second <br />• Third <br />• Fourth <br />• Fifth <br />• Sixth <br />NFPA 1, Fire Code, Chapter 12.7.3.2.2 <br />VIOLATION 5 <br />There is not a secondary exit from the following floors. <br />• Second <br />• Third <br />• Fourth <br />• Fifth <br />• Sixth <br />NFPA 1, Fire Code, Chapter 14.9.1.1 <br />VIOLATION 6 <br />The exit lights in the bank area of the first floor did not work when tested. <br />NFPA 1, Fire Code, Chapter 4.5.8.1 <br />VIOLATION 7 <br />Inspection Number RR015800A Page 2 of 5 <br />Revised 12/2014 <br />