Laserfiche WebLink
Section 903.2, Where required, shall be amended to read as follows and to <br />delete the exception: <br />"903.2 Where required. Approved automatic sprinkler systems in <br />new buildings and structures shall be provided in the locations described in <br />Sections 903.2.1 through 903.2.12. <br />"Automatic Sprinklers shall not be installed in elevator machine <br />rooms, elevator machine spaces, and elevator hoistways, other than <br />pits where such sprinklers would not necessitate shunt trip <br />requirements under any circumstances. Storage shall not be allowed <br />within the elevator machine room. Signage shall be provided at the <br />entry doors to the elevator machine room indicating 'ELEVATOR <br />MACHINERY - NO STORAGE ALLOWED. "' <br />Section 903.2.9, Group S -1, shall be amended by adding Section 903.2.9.3, Self - <br />service storage facility, to read as follows: <br />"903.2.9.3 Self- Service Storage Facility. An automatic sprinkler <br />system shall be installed throughout all self - service storage facilities." <br />Section 903.2.11, Specific buildings areas and hazards, shall be amended by <br />amending Section 903.2.11.3 and by adding Sections 903.2.11.7, 903.2.11.8, and <br />903.2.11.9 to read as follows: <br />"903.2.11.3 Buildings 35 feet or more in height. An automatic <br />sprinkler system shall be installed throughout buildings that have one or <br />more stories, other than penthouses in compliance with Section 1510 of the <br />International Building Code, located 35 feet (10 668 mm) or more above the <br />lowest level of fire department vehicle access, measured to the finished floor. <br />"Exception: Open parking structures in compliance with Section <br />406.5 of the International Building Code, having no other occupancies <br />above the subject garage." <br />Sections 903.2.11.4- 903.2.11.6 remain unchanged. <br />"903.2.11.7 High -Piled Combustible Storage. For any building <br />with a clear height exceeding 12 feet (4572 mm), see Chapter 32 to <br />determine if those provisions apply. <br />"903.2.11.8 Spray Booths and Rooms. New and existing spray <br />booths and spraying rooms shall be protected by an approved automatic <br />fire - extinguishing system. <br />25 <br />