[F] When located on the ground level at an exterior wall the fire pump room shall be provided with an <br />exterior fire department access door that is not less than 3 ft. in width and 6 ft — 8 in in height regardless <br />of any interior doors that are provided. A key box shall be provided at this door, as required by Section <br />506.1. <br />Exception: When it is necessary to locate the fire pump room on other levels or not at an exterior <br />wall the corridor leading to the fire pump room access from the exterior of the building shall be <br />provided with equivalent fire resistance as that required for the pump room or as approved by the fire <br />code official. Access keys shall be provided in the key box as required by Section 506.1. <br />Section 1006.2.2., Egress based on use, shall be amended by adding a new Section 1006.2.2.6 as <br />follows: <br />1006.2.2.6 Electrical Rooms. For electrical rooms special exiting requirements may apply. Reference <br />the electrical code as adopted. <br />Section 1009. 1, Accessible means of egress required, shall be amended by adding the following <br />Exception 4 to read as follows: <br />1009.1 Accessible means of egress required. . <br />{Section 1009.1 and Exceptions 1 -3 remain unchanged.} <br />Exceptions: <br />4. Buildings regulated under State Law and built in accordance with State registered plans including <br />any variances or waivers -granted by the State, shall be deemed to be in compliance with the <br />requirements of Section 1009. <br />Section 1010.1.9.4 Bolt Locks, shall be amended to amend Exceptions 3 and 4 as follows: <br />1010.1.9.4, Bolt locks.... <br />{Section 101.1.9.4 and Exceptions 1 and 2 remain unchanged.} <br />Exceptions: <br />3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F, M or S <br />occupancy, manually operated edge- or surface- mounted bolts are permitted on the inactive leaf. <br />The inactive leaf shall not contain doorknobs, panic bars or similar operating hardware. <br />4. Where a pair of doors serves a Group A, B, F, M or S occupancy manually operated edge- or <br />surface - mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed <br />to meet egress capacity requirements and the building is equipped throughout with an automatic <br />sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall not contain <br />doorknobs, panic bars or similar operating hardware. <br />{Exception 5 remains unchanged.} <br />Section 1015.8, Window openings, shall be amended to amend subsection 1. To read as follows: <br />1015.8 Window Openings. ... <br />1. Operable windows where the top of the sill of the opening is located more than 75 feet (" 860 mFn) 55 <br />feet (16 764 mm) above the finished grade or other surface below and that are provided with window fall <br />prevention devices that comply with ASTM F 2006. <br />{Remainder of Section 1015.8 remains unchanged.} <br />12 2015 IBC Amendments <br />