such sprinklers would not necessitate shunt trip requirements under <br />any circumstances. Storage shall not be allowed within the elevator <br />machine room. Signage shall be provided at the entry doors to the <br />elevator machine room indicating `ELEVATOR MACHINERY - NO <br />STORAGE ALLOWED."' <br />Section 903.2.9, Group S-1, shall be amended by adding Section 903.2.9.3, Self- <br />service storage facility, to read as follows: <br />"903.2.9.3 Self -Service Storage Facility. An automatic sprinkler <br />system shall be installed throughout all self-service storage facilities with <br />interior access corridors." <br />Section 903.2.11, Specific buildings areas and hazards, shall be amended by <br />amending Section 903.2.11.3 and by adding Sections 903.2.11.7, 903.2.11.8, and <br />903.2.11.9 to read as follows: <br />"903.2.11.3 Buildings 35 feet or more in height. An automatic <br />sprinkler system shall be installed throughout buildings that have one or more <br />stories, other than penthouses in compliance with Section 1510 of the <br />International Building Code, located 35 feet (10 668 mm) or more above the <br />lowest level of fire department vehicle access, measured to the finished floor. <br />"Exception: Open parking structures in compliance with Section <br />406.5 of the International Building Code, having no other occupancies <br />above the subject garage." <br />Sections 903.2.11.4-903.2.11.6 remain unchanged. <br />"903.2.11.7 High -Piled Combustible Storage. For any building <br />with a clear height exceeding 12 feet (4572 mm), see Chapter 32 to <br />determine if those provisions apply. <br />"903.2.11.8 Spray Booths and Rooms. New and existing spray <br />booths and spraying rooms shall be protected by an approved automatic <br />fire -extinguishing system. <br />•! <br />_ ... <br />_ ... <br />24 <br />