Section 903.3.5 Water supplies. Water supplies for automatic sprinkler systems shall comply with this <br />section and the standards referenced in Section 903.3.1. The potable water supply shall be protected <br />against backflow in accordance with the requirements of this section and the International Plumbing Code. <br />For connections to public waterworks systems, the water supply test used for design of fire protection <br />systems shall be adjusted to account for seasonal and daily pressure fluctuations based on information <br />from the water supply authority and as approved by the fire code official. <br />[F] Water supply asrequiredITITITforwwwwsuch s stems shall be rovided in conformance with the _suoa <br />requirements of the respective standards: however, ever ITwater-based fire protection s ptem shall be <br />designed with a 10 psi safety factor. Reference Section 507.4 for additionalw_desinn requirements. <br />Section 903.4, Sprinkler systems supervision and alarms shall be amended to add a second <br />paragraph after the Exceptions to read as follows: <br />[F] Srrinklerwand standpipe system water-flowdetectorsshall be provided for each floor tap to the sprinkler <br />system and shall cause an alarm upon detection of water flow for more than 45 seconds. All control valves <br />inthesprinkler and standpipe systems except for fire department hose µconnection valves shall be <br />electncallywsupervised to initiate a supervisorY.§1nnalwat_the central station upon tamperlM <br />Section 903.4.2, Alarms, shall be amended to read as follows: <br />Section 903.4.2. Alarms. An approved audible device, located on the exterior of the building in an <br />approved location, shall be connected to each automatic sprinkler system. Such sprinkler waterflow alarm <br />devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice <br />size installed in the system. Where a fire alarm system is installed, actuation of the automatic sprinkler <br />system shall actuate the building fire alarm system. <br />F T uiq red o„q.ltp exterior of the building shal�a weatherproof horn/strobenotificatio,n <br />._ e alarm device re <br />araoliance with a minimum 75 candela strobe ratina, installed as close as_practicable to the fire_ department <br />connection. <br />Section 905.2, Installation standard, shall be amended to read as follows: <br />[F] 905.2 Installation standard. Standpipe systems shall be installed in accordance with this section and <br />NFPA 14. Manual dfy,_stand i e s stems shall be su ervised with a minimum of 10 psig and a maximum <br />of 40 psig air pressure withITg high/low alarm. <br />Section 905.3, Required installations, shall be amended by adding Section 905.3.9, Buildings <br />exceeding 10,000 sq. ft., and exceptions to read as follows: <br />[F] 905.3.9 Buildin s exceedin 10.000 s . ft. In buildin s exceeding 10 000 s uare feet in area Der story <br />and where any portion of the building s interior area is more than 200 fe@L60960 mm) of travel verticalhy <br />and horizontally, from the nearest r oint of fireITdepertment vehicle access ClassITI automatic wet or manual <br />wet standTri�es_shall be provided.., <br />Exceptions:_, <br />1. Automatic -dry and semi-automatic dFY standpipes are allowed as provided for in NFPA 14. <br />2. R-2 occupancies of four stories or less in hei ht havin no interior corridors. <br />Section 905.4, Location of Class I standpipe hose connections, shall be amended to read as follows: <br />Section 905.4, Location of Class I standpipe hose connections. Class I standpipe hose connections <br />shall be provided in all of the following locations: <br />[F] 1. In every required interieFexit stairway, a hose connection shall be provided for each story above <br />and below grade plane. Hose connections shall be located at an intermediate landing between <br />stories, unless otherwise approved by the fire code official. <br />2. On each side of the wall adjacent to the exit opening of a horizontal exit. <br />Exception: Where floor areas adjacent to a horizontal exit are reachable from an interior exit <br />stairway hose connection by a 30 -foot (9144 mm) hose stream from a nozzle attached to 100 feet <br />(30 480 mm) of hose, a hose connection shall not be required at the horizontal exit. <br />7 2015 IBC <br />Amendments <br />