water main and the pumps. Each connection and the supply piping between the connection and the <br />pumps shall be sized to supply the flow and pressure required for the pumps to operate. <br />Exception: Two connections to the same main shall be permitted provided the main is valved <br />such that an interruption can be isolated so that the water supply will continue without interruption <br />through no fewer than one of the connections. <br />Section 404.5, Smoke control, shall be amended by deleting the Exception. <br />Section 406.3.5.1 Carport separation, shall be amended to read as follows: <br />406.3.5.1 Carport separation. A separation is not required between a Group R-3 and U carport, provided <br />the carport is entirely open on two or more sides and there are not enclosed areas above. A fire <br />§pparaation_is not, recui ed between a Group R-2 and U car ort provided that the car ort is entirely open <br />on all sides and that the distance between the two is at least 10 feet 3048 rn <br />Section 506.3.2, Minimum frontage distance, to add Section 506.3.2.1, Open space limits, to read <br />as follows: <br />506.3.2.1 Open Space Limits. Such open space shall be either on the same lot or dedicated for public <br />use and shall be accessed from a street or approved fire lane. I_n order to be considered as accessible, if <br />not in direct contact with a street or fire lane a minimum 10-footmwide nathwa meeting fire department <br />access from the street or approved fire lane shall be provided. <br />Section 712.1.9, Two-story openings, shall be amended to amend item 4 to read as follows: <br />4. Is not open to a corridor in Group I and R H occupancies. <br />Section 901.6.1, Automatic sprinkler systems, shall be amended to add Section 901.6.1.1, <br />Standpipe testing, to read as follows: <br />901.6.1.1 Stand ipe testin . Buildin owners/mana ers must maintain and test stand i e s stems as„ger <br />NFPA 25_reguirements The following, additional requirements shall be applied to thewtestina that is reguired <br />every 5 years: <br />1. The piping between the ,Fire Department Connection_(FDC) and the standpipe shall be backflushed <br />when foreign material is resent, and also hydrostaticallyr tested for all FDC's on an ty�r e of stand i e, <br />system. Hydrostatic testing shall also be conducted in accordance with__NFP,A 25 requirements for <br />the different types of standpipe systems. <br />2. For any manual W'dry or wet) standpi °e s stem not having an automatic_ water supply capable of <br />flowin water through the stand i e the tester shall connect hose from a fire hydrant or portable <br />gwumpinq system as approved by the fire code officiaL to each FDC and flow water through the <br />standpipe system to the roof outlet toITvenfy that each inlet connection functions pEoperhv,; Confirm that <br />there are no oxen hose. aly@§ priorwto introducing water into a dr stand Ike. There is no required <br />pressure criteria at the outlet. Verify that checkwwvalves function properly and that there are no closed <br />control valves on the system.. <br />.. <br />3. AnyIT rp essure relief, reducinc or control valves shall be testedmminmmaccordance with the re iuirements <br />of NFPA 25. All hose valves shall be exercised. <br />4. If the FDC is not mmalread,provided with approved caps, the contractor shall installsuchcasa�for all <br />FDC's as reauired by the fire code official <br />5. Upon successful completion of stand pip test�place a blue tags as per Texas Administrative Code, <br />Fiwre.Sorinkler Rules for Inspection, Test and Ma mtenance_Service HTM) Tag)at the bottom of each <br />standpi a riser in the building. The tag shall be check -marked as "Fifth Year' for Type of ITM, and <br />the note on the back of the tac shall read "5 Year Standpipe Test” at a minimum., <br />6.The procedures re uiredITITbw Texas Administrative Code Fire S rinkler Rules with re ash rd to Yellow <br />Tags and Red Tags or any deficiencies noted during the testing includin the required notification <br />of the local Authority Havingjq[[gdiction (fire code official) shall be followed. <br />4 2015 IBC <br />Amendments <br />