Laserfiche WebLink
S. Upon successful completion of standpipe test, place a blue tag (as per Texas Administrative <br />Code, Fire Sprinkler Rules for Inspection, Test and Maintenance Service (ITM) Tag) at the <br />bottom of each standpipe riser in the building. The tag shall be check -marked as "Fifth Year" for <br />Type of ITM, and the note on the back of the tag shall read "5 Year Standpipe Test" at a minimum. <br />6. The procedures required by Texas Administrative Code Fire Sprinkler Rules with regard to <br />Yellow Tags and Red Tags or any deficiencies noted during the testing, including the required <br />notification of the local Authority Having Jurisdiction (fire code official) shall be followed. <br />7. Additionally, records of the testing shall be maintained by the owner and contractor, if <br />applicable, as required by the State Rules mentioned above and NFPA 25. <br />8. Standpipe system tests where water will be flowed external to the building shall not be <br />conducted during freezing conditions or during the day prior to expected night time freezing <br />conditions. <br />9. Contact the fire code official for requests to remove existing fire hose from Class II and III <br />standpipe systems where employees are not trained in the utilization of this firefighting <br />equipment. All standpipe hose valves must remain in place and be provided with an approved cap <br />and chain when approval is given to remove hose by the fire code official. <br />Add Section 901.6.4, False alarms and nuisance alarms, to read as follows: <br />901.6.4 False Alarms and Nuisance Alarms. False alarms and nuisance alarms shall not be <br />given, signaled or transmitted or caused or permitted to be given, signaled or transmitted in any <br />manner. <br />Amend Section 901.7, Systems out of service, to read as follows: <br />901.7 Systems out of service. Where a required fire protection system is out of service or in the <br />event of an excessive number of activations, the fire department and the fire code official shall <br />be notified immediately and, where required by the fire code official, the building shall either <br />be evacuated or an approved fire watch shall be provided for all occupants left unprotected by <br />the shut down until the fire protection system has been returned to service.... (Remaining text <br />unchanged) <br />Amend Section 903.1.1, Alternative protection, to read asfollows: <br />903.1.1 Alternative protection. Alternative automatic fire -extinguishing systems complying <br />with Section 904 shall be permitted in addition to automatic sprinkler protection where <br />recognized by the applicable standard, or as approved by the fire code official. <br />