Laserfiche WebLink
Amend Section 903.2, Where required, to add the following paragraph and delete the Exception for <br />telecommunications buildings: <br />Section 903.2 Where required. <br />Automatic Sprinklers shall not be installed in elevator machine rooms, elevator machine spaces, <br />and elevator hoistways, other than pits where such sprinklers would not necessitate shunt trip <br />requirements under any circumstances. Storage shall not be allowed within the elevator machine <br />room. Signage shall be provided at the entry doors to the elevator machine room indicating <br />"ELEVATOR MACHINERY -NO STORAGE ALLOWED." <br />{Delete Exception.{ <br />Amend Section 903.2.4.2, Group F-1 distilled spirits, to read asfollows: <br />903.2.4.2 Group F-1 distilled spirits. An automatic sprinkler system shall be provided <br />throughout a Group F-1 fire area used for the manufacture of distilled spirits involving more than <br />120 gallons of distilled spirits (>16% alcohol) in the fire area at any one time. <br />Amend Section 903.2.9.3, Group S-1 distilled spirits or wine, to read as follows: <br />903.2.9.3 Group S-1 distilled spirits or wine. An automatic sprinkler system shall be provided <br />throughout a Group S-1 fire area used for the bulk storage of distilled spirits or wine involving <br />more than 120 gallons of distilled spirits or wine (>16% alcohol) in the fire area at any one time. <br />Amend Section 903.2.9.4, Group S-1 upholstered furniture and mattresses, to delete the exception <br />Add Section 903.2.9.5, Self-services storage facility, to read as follows: <br />903.2.9.5 Self-service storage facility. An automatic sprinkler system shall be installed <br />throughout all self-service storage facilities. <br />Exception. Self-service storage facilities with fire area not exceeding 2,500 sq ft and not greater <br />than 1 story above grade plane where all storage spaces are accessed directly from the exterior. <br />Amend Section 903.2.11 by amending Section 903.2.11.3, Buildings 35 feet or more in height, and by <br />adding Sections 903.2.11.7, High -piled combustible storage; 903.2.11.8, Spray booths and rooms; and <br />903.2.11.9, Buildings over 6,000 sq. ft. as follows: <br />903.2.11.3 Buildings 35 feet or more in height. An automatic sprinkler system shall be installed <br />throughout buildings that have one or more stories other than penthouses in compliance with <br />