Laserfiche WebLink
Amend Figure R602.6.1, TOP PLATE FRAMING TO ACCOMMODATE PIPING, by deleting <br />the Eiaure and inserting the followingCiaure in its place: <br />TX,F <br />AND 5 M. GWR]E <br />INFO ACROSS ANO <br />"EACH SIDEOF THE <br />d NAZSE CKSOE <br />Add section R703.8.4.1.2, Veneer ties for wall studs: to read as follows: <br />R703.8.4.1.2 Veneer ties for wall studs. In stud framed exterior walls, all ties <br />may be anchored to studs as follows: <br />1. When studs are 16 in (407 mm) o.c., stud ties shall be spaced no further <br />apart than 24 in (737 mm) vertically starting approximately 12 in (381 mm) <br />from the foundation; or <br />2. When studs are 24 in (610 mm) o.c., stud ties shall be spaced no further <br />apart than 16 in (483 mm) vertically starting approximately 8 in (254 mml <br />from the foundation. <br />Amend Section M1305.1.2, Appliances in attics, to read as follows: <br />M1305.1.2 Appliances in attics. Attics containing appliances shall be provided. <br />.. [bulk of paragraph unchanged] ... side of the appliance. The clear access <br />opening dimensions shall be a minimum of 20 inches by 30 inches (508 mm bX <br />762 mm), and large enough to allow removal of the largest appliance. As a <br />minimum, for access to the attic space, provide one of the following_ <br />1. A permanent stair. <br />2. A pull down stair with a minimum 300 lb (136 kg) capacity. <br />3. An access door from an upper floor level. <br />Exceptions: [Exceptions unchanged.] <br />29 <br />