approved degree of detail that allows each circuit to be distinguished from all <br />others. Spare positions that contain unused overcurrent devices or switches <br />shall be described accordingly. The identification shall be included in a circuit <br />directory that is located on the face or inside of, or in an approved location <br />adjacent and permanently affixed the panel door in the case of a panelboard <br />and at each switch or circuit breaker in a switchboard or switchgear. No circuit <br />shall be described in a manner that depends on transient conditions of <br />occupancy. <br />[Subsection B. Source of Supply, remains unchanged.[ <br />Amend Article 410.118, Access to Other Boxes, to read as follows: <br />410.118 Access to Other Boxes. <br />Luminaires recessed in the ceilings, floors, or walls shall not be used to access <br />outlet, pull, or junction boxes or conduit bodies, unless the box or conduit body is <br />an integral part of the listed luminaire. <br />Exception: removable luminaires with a minimum measurement of 22 in. X 22 in. <br />shall be permitted to be used as access to outlet, pull, junction boxes or conduit <br />bodies. <br />Amend Article 422.31 B. Appliances Rated Over 300 Volt -Amperes, to read as follows: <br />422.31 B Appliances Rated Over 300 Volt -Amperes. <br />(B) Appliances Rated over 300 Volt -Amperes. For permanently connected <br />appliances rated over 300 volt-amperes, the branch -circuit switch or circuit <br />breaker shall be permitted to serve as the disconnecting means where the switch <br />or circuit breaker is within sight from and is readily accessible to the appliance it <br />serves or is capable of being locked in the open position in accordance with 110.25 <br />and is readily accessible to the appliance it serves. <br />Informational Note No. 1: For appliances employing unit switches. see 422.34. <br />Informational Note No 2: The following means of access are considered to <br />constitute readily accessible for this code change when conforming to the <br />additional access requirements of the 1 Codes: <br />(1) A permanent stair. <br />(2) A pull-down stair with a minimum 300 lb. (136 kg) capacity. <br />(3) An access door from an upper floor level. <br />Amend Article 500.8, Equipment, Subsection A(3) to read as follows: <br />500.8 Equipment. <br />[Existing text unchanged through Subsection A(2 . <br />REV <br />