Laserfiche WebLink
interface device may be wired C1a55..B,...provided. the distance from the interface <br />device to the..nitiatin...device is ten, feet or less. <br />Amend Section 90Z6.3 Initiating device ident rcation b_deletin all „dour Exce))tions. <br />Amend Section 907.6.6..... Monitoring to add the JbIlowina sentence at end of the <br />paragraph: <br />907.6.6 Monitor in Existin text unchan ped. , . See 907.6.3 for the reg; u iced <br />information transmitted to the sut)ervising station. <br />Amend Section 910.2,Where reaWn d to read as ollows: <br />910.2 Where req- .--d. Smoke and heat vents or a mechanical smoke removal <br />s std em shall be.nstalled as req uired b-SectionsIT910.2.1910.2.2, and 910.3.2. <br />Exce tions <br />1. [Exception 1 remains unchanged.] <br />2. Only manual smoke and heatremovalshall not be re.uired in areas of <br />buildinasIT e ui , ed with early.._sup - ression fast -response... ESFR s ;�rmklers. <br />Automatic smoke and heat removal is prohibited. <br />3. .....Only manual smoke and heat removal shall not be re( u�.ired in areas of <br />buildings .eauLed with control ,mode special a 1 Caton., s.rnklersIT.with a <br />response time index of 50 m*S 1L2 or less that are listed to control a fire in <br />stored commodities... with 12 or fewer sprinklers. Automatic smoke and heat <br />removal is prohibited. <br />Add Section 910.2.3, Group LH burldin s, to read as follows: <br />910.2.3 GroUD H. buildings. Grog H buildings and portions thereof used as a <br />GrQW) H occupancy as follows: <br />1. In occu nancies, classified as Grouj .m H-2 or H-3, an of which are more <br />than 15,000 square feet 1394 m2 in single floor area. <br />Excen)tion ._ Buildings of noncombustible construction containing only, <br />noncombustible materials. <br />2._ In areas of buildings in Group H used for storing Class 2,W 3 ..An 4 mli jj id <br />and solid oxidizers, Clasp s 1,and unclassified detonable organic peroxides Class. <br />3 and 4 unstable (reactive;),ITmaterials o,r.Class 2 or 3 water -reactive materials <br />as reuired for..a.bj h hazard co_mmodi y classification. <br />Excelaaon Buildin Wsof noncombustible construction containing... only <br />noncombustible materials., <br />19 <br />