Laserfiche WebLink
<br />ATTACHMENT "A" <br />CHANGE ORDER NO. 1 <br /> <br />Contract Title: Wastewater Pumping Station <br />Contract Number: 15-85-20-0341 <br /> <br />1. Instrumentation and Controls: <br /> <br />No changes in the requirements of the <br />Contract Documents <br /> <br />Oeduction $ 5,600.00 <br /> <br />2. Sluice Gates: <br /> <br />Section 11202, 1.5 Sluice Gates, E. <br /> <br />Change the schedule for SV-l, SV-2 and SV-3 to <br /> <br />Read: "Seating head: 30 feet <br />Unseating head: 20 feet <br />Max. Operating head: 20 feet" <br /> <br />Deduction $ 4,214.00 <br /> <br />3. Pipe and Fittings <br /> <br />Section 11205 <br /> <br />2.1 Delete the last sentence; cast iron fittings will <br />be acceptable with ductile iron pipe. <br /> <br />2.3 In the fi rst paragraph, change".... cl ass number 52." <br />to read "....class number 50." <br /> <br />3.3 B.l.c. delete the second sentence; restrainer glands <br />will be permitted. <br /> <br />Deduction $ 2,689.00 <br /> <br />4. Building: <br /> <br />The building shall be constructed of 8-inch concrete <br />masonry units with a nominal 6-inch reinforced concrete <br />roof. The general arrangement shall be as shown in the <br />