Laserfiche WebLink
interface device may be wired Class B, provided the distance from the interface <br />device to the initiating device is ten feet or less. <br />Amend Section 907.6.3, Initiating device identification, by deleting all four Exceptions. <br />Amend Section 907.6.6. Monitoring, to add the following sentence at end of the <br />paragraph: <br />907.6.6 Monitoring. [Existing text unchanged.] ... See 907.6.3 for the required <br />information transmitted to the supervising station. <br />Amend Section 910.2, Where required, to read as follows: <br />910.2 Where required. Smoke and heat vents or a mechanical smoke removal <br />system shall be installed as required by Sections 910.2.1, 910.2.2, and 910.3.2. <br />Exceptions: <br />[Exception 1 remains unchanged.] <br />2. Only manual smoke and heat removal shall not be required in areas of <br />buildings equipped with early suppression fast -response (ESFR) sprinklers. <br />Automatic smoke and heat removal is prohibited. <br />3. Only manual smoke and heat removal shall not be required in areas of <br />buildings equipped with control mode special application sprinklers with a <br />response time index of 50(m*S)112 or less that are listed to control a fire in <br />stored commodities with 12 or fewer sprinklers. Automatic smoke and heat <br />removal is prohibited. <br />Add Section 910.2.3, Group H buildings, to read as follows: <br />910.2.3 Group H. buildings. Group H buildings and portions thereof used as a <br />Group H occupancy as follows: <br />1. In occupancies classified as Group H-2 or H-3, any of which are more <br />than 15.000 square feet (1394 m2) in single floor area. <br />Exception: Buildings of noncombustible construction containing only <br />noncombustible materials. <br />2. In areas of buildings in Group H used for storing Class 2. 3. and 4 liquid <br />and solid oxidizers. Class 1 and unclassified detonable organic peroxides. Class <br />3 and 4 unstable (reactive) materials, or Class 2 or 3 water -reactive materials <br />as required for a high -hazard commodity classification. <br />Exception: Buildings of noncombustible construction containing only <br />noncombustible materials. <br />19 <br />