Laserfiche WebLink
Amend Section 910.4.3. 1, Makeup Air, to read as follows: <br />910.4.3.1 Makeup air. Makeup air openings shall be provided within 6 feet (1829 <br />mm) of the floor level. Operation of makeup air openings shall be automatic. The <br />minimum gross area of makeup air inlets shall be 8 square feet per 1.000 cubic <br />feet per minute (0.74 m2 per 0.4719 m3/s) of smoke exhaust. <br />Amend Section 912.2, Location, by adding Section 912.2.3, Hydrant distance, to read as <br />follows: <br />912.2.3 Hydrant distance. An approved fire hydrant shall be located within 100 <br />feet of the fire department connection as the fire hose lays along an unobstructed <br />path. <br />Amend Section 913.2.1, Protection of fire pump rooms, by adding Section 913.2.1.1, Fire <br />pump room access, and Exception to read as follows: <br />913.2.1.1 Fire pump room access. When located on the ground level at an <br />exterior wall, the fire pump room shall be provided with an exterior fire <br />department access door that is not less than 3 ft. in width and 6 ft. - 8 in. in height, <br />regardless of any interior doors that are provided. A key box shall be provided at <br />this door, as required by IFC Section 506.1. <br />Exception: When it is necessary to locate the fire pump room on other levels or <br />not at an exterior wall, the corridor leading to the fire pump room access from the <br />exterior of the building shall be provided with equivalent fire resistance as that <br />required for the pump room, or as approved by the fire code official. Access keys <br />shall be provided in the key box as required by IFC Section 506.1. <br />Amend Section 1006.2.1, Egress based on occupant load and common path of egress <br />travel distance to amend Exception 3 to read as follows: <br />1006.2.1 Egress based on occupant load and common path of egress travel <br />distance. [Existing text unchanged. <br />Exceptions: <br />3. Unoccupied rooftop mechanical rooms and penthouses are not required to <br />comply with the common path of egress travel distance measurement. <br />Amend Section 1009.8, Two-way communication, by adding the followincr Exception 7: <br />1009.8 Two-way communication. [Existing text unchanged.] <br />20 <br />